D9412GV4/D7412GV4/D7212GV4 | Owner's Manual Supplement
Bosch Security Systems, Inc. | 9/11 | F01U245224-02 31
3.6.3 Alarms Acknowledged within the Abort Window
If the end user acknowledges an alarm within the Abort Window:
The alarm output is silenced.
No alarm, restoral, or cancel reports are sent.
No alarm, restoral, or cancel reports are entered in the control
panel event log.
3.6.4 At the End of the Alarm Abort Window
If no user acknowledges the alarm within the Alarm Abort Window,
the control panel sends the appropriate alarm reports.
3.7 Cancel Report and Cancel Window
If a user acknowledges an alarm after the Abort Window expires,
but before Bell Time expires, the control panel sends a Cancel
Report. The Cancel Window starts when the alarm is sent and
stops when the Alarm Bell timer expires or a user acknowledges
an alarm.
3.8 Duress Alarm
This feature allows any passcode with the Send Duress permission
enabled to always send a Duress Alarm event upon entry. The
Duress Alarm feature allows an installation to allocate unique
passcodes as the main duress passcodes for all users.
Additionally, when the SIA CP-01 compliant Duress Alarm option is
enabled, the Passcode +1 and +2 options are disabled.
3.9 Swinger Shutdown
This feature allows for a control panel to automatically bypass a point
that reports two or more alarm or trouble events within the same arm
cycle. The maximum number of faults allowed on a point is called the
Swinger Count. This value was set by the installer.