Vista de pagina 14
D9412GV4/D7412GV4/D7212GV4 Setting Up Points and Outputs | en 15
Bosch Security Systems, Inc. Quick Reference Guide F01U215242 | 01 | 2011.10
Table 6.5 Point Response Selections
Point Response
Selections*
0123456789ABCDEF
Armed OpenIIIIDDIIDIIIIIT
ShortIIIIIIDDDI IIIII
Disarmed Open T T T I I T I T
Short T T T I T I I
24-HourOpenITIT ITSTS S N/A
ShortI I TTI T TS SS
*Selections: D = Delayed Response, I = Instant Alarm, S = Supervisory, T = Trouble, B = No
Response