Technical Features:
1200 Series 5000 Series
Loops 1 to 2 1 to 32
Elements per loop Up 127 Up to 254
Elements per system up to 254 up to 4064
(networked 2032)
Max. loop length 1600 m 3000 m
Max. loop power 300 mA 1500 mA
Addressable and conventional
detectors in one system
Modules per panel up to 6 up to 46 per panel
Remote keypads up to 3
Panel network no
Connection via fiber optics or
standard fire cable
Modular Fire Panel 5000 Series:
Standalone or networked solution with CAN-Bus technology - with up
to 32 loops for each panel, the ideal solution for medium-size to large
applications
Fire Panel 1200 Series:
Standalone version with 2 x 127 addressable elements - ideal for
small applications
5000 Series
Remote
Keypad
CAN-Bus
1200 Series/
5000 Series
LSN loop
Smoke Detectors
Aspirating Smoke
Detectors
Sounders
Manual Call Points
Interfaces
Connectable to 1200 Series 5000 Series
EVAC System from Bosch
(via serial interface)
Building Management System from Bosch
(OPC/Ethernet)
Fire Monitoring System from Bosch
(4A/MTS)
Paging and DECT Systems from Bosch
(and third-party)
Remote
Keypad
Comentarios a estos manuales