8 | INSTALLING THE FREEZE SENSOR DDC Field Installation Guide
DDC Field Installation Guide8 733 904 851 Revised 05-13 Subject to change without prior notice
INSTALLING THE FREEZE SENSOR
1. Route the provided freeze sensor to the
refrigeration line of the water coil. (Figure #7)
Figure # 7
2. Use the two(2) supplied tie-wraps to mount
the sensor. (Figure #8)
Figure # 8
3. Use the provided cork tape to wrap the
sensor.(Figure #9)
4. Apply the provided pipe insulating tape to
provide good thermal connection to the
sensor. (Figure #4)
Figure # 9
5. Connect the terminated ends of the sensor
wires to the UPM board at the location(s)
specified in Figure #1 & #2;
For UPM-I units connect the sensor on the
water coil to Freeze 1.
For UPM-II units connect the sensor on the
water coil of the first compressor to Freeze
1, and connect the sensor on the water coil
of the second compressor to Freeze 2.
UPM TO DDC ALARM CONNECTION
1. Locate the Alarm (ALR) Contacts on the
corresponding UPM-I or UPM-II board per
Figure #1 & #2.
2. Connect the cables labeled OUT and COM from
the DDC wiring harness to the spade
connectors labeled OUT and COM on the UPM
board.
If the unit is already equipped with the
freeze sensor option, verify sensor
location per Figure #7 and skip the
following steps.
There is no polarity for these wires.