• DOK-DIAX01-MAIN+2AD+1M-ANW1-EN-E1,44 • 07.97
3. Controller Functions
3.11 Temperature Pre-Warning
Due to the overload capacity of the main drives, load cycles can be used
which need more than the continuous power from the drive for short
periods. Choice of correct drive size ensures that the temperature of
motor and controller is always in the permissible temperature range. If,
though, the cooling system of motor or controller is not operating
correctly (dirt, etc.), there is a risk of damage to the drive from overheating.
INDRAMAT main spindle drives are protected against overheating:
If the motor or controller temperature approaches the limit of the
temperature range, this is signalled to tyhe controller via the
TEMPWARN alarm output. If the alarm is caused by the motor
temperature, the message MOTWARN appears in the display.
KKWARN appears if it is caused by the controller.
The drive is switched off automatically if the load is not removed and
the temperature continues to rise.
Temperaturvorwarnun
g
Table:
permissible
temperature range
Motor: 0° <
ϑ
< 155°C
Control:
Legend:
1 = +24V
0 = 0V
= signal step
= any control
state
^
^
^
^
27
23
24
25
26
28
29
30
31
32
33
34
35
36
37
3
1
1
POS 2
E-STOP (RAC only)
RF
RUN
POS 1
MD-RED
OSCILATE
PAR 1
PAR 2
LIMIT 1
LIMIT 2
LIMIT 4
SPEED 1
SPEED 2
EXT POS
AS (KDA/TDA only)
1
0
X2 control inputs
control unit
X2 signal output
9 TEMP WARN
0 =temperature pre-warning
has been actuated
control unit
^
signal
thresholds
0° <
ϑ
<
ϑ
maxperm
145°C
ϑ
maxperm
Figure 66: Control inputs and signal output for temperature pre-warning
If KKWARN appears in the display, the drive switches off after 30
seconds and KKTEMP appears in the display.
Drive torque is immediately limited to 50% when KKWARN
appears!
If MOTWARN (winding temperature 145°C) appears and the temperature
continues to rise, the drive switches off at a windings temperature of
155°C and MOTTEMP then appears in the display.
With no temperature sensor connected, the TEMPWARN output is also
active after ten minutes with at least 10% loading. NO TEMP appears in
the display and the drive switches off.
NO TEMP
MOT WARN
KK WARN
MOT TEMP
KK TEMP
Heatsink pre-warning
Motor temperature
pre-warning
Wire break monitoring
Possible error messages in
the display
Protection against
overheating