DS7445i/V2-EXP, DS7447E/V2-EXP | Installation Instructions | 2.0 Keypad Addresses EN | 3
Bosch Security Systems | 4/04 | 4998122645D
Figure 3: Internal View of DS7447E and
DS7447V2 Keypads
A DD R E SS
1 2 4 8 1 6
M O D E
2 1
3 4 5
1 – Address jumper pins
2 – Mode pins
3 – Sounder
4 – Option bus terminals
5 – Contrast control
Figure 4: Shorting Jumper Placements
1 2
1 – Jumper Plug ON (covers both pins)
2 – Jumper Plug OFF (3 possible configurations)
Table 2: Keypad Address Selections for
DS7060, DS7080i Series, and
DS7400Xi Series Control Panels
Address JumpersModule
Address
1 2 4 8 18 Mode
0 OFF OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF OFF
2 OFF ON OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF
4 OFF OFF ON OFF OFF OFF
5 ON OFF ON OFF OFF OFF
6 OFF ON ON OFF OFF OFF
7 ON ON ON OFF OFF OFF
8 OFF OFF OFF ON OFF OFF
9 ON OFF OFF ON OFF OFF
10 OFF ON OFF ON OFF OFF
11 ON ON OFF ON OFF OFF
12 OFF OFF ON ON OFF OFF
13 ON OFF ON ON OFF OFF
14 OFF ON ON ON OFF OFF
15 ON ON ON ON OFF OFF
Table 3: Keypad Address Selections for
DS7200/DS7200V2 Series Control
Panels
Address JumpersModule
Address
1 2 4 8 18 Mode
0* OFF OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF ON
2 OFF ON OFF OFF OFF ON
3 ON ON OFF OFF OFF ON
4 OFF OFF ON OFF OFF ON
5 ON OFF ON OFF OFF ON
6 OFF ON ON OFF OFF ON
7 ON ON ON OFF OFF ON
8 OFF OFF OFF ON OFF ON
9 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF ON
15 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON ON
23 ON ON ON OFF ON ON
24 OFF OFF OFF ON ON ON
25 ON OFF OFF ON ON ON
26 OFF ON OFF ON ON ON
27 ON ON OFF ON ON ON
28 OFF OFF ON ON ON ON
29 ON OFF ON ON ON ON
30 OFF ON ON ON ON ON
31 ON ON ON ON ON ON
32 OFF OFF OFF OFF OFF ON
*Installer’s Mode Address Setting: Use for direct
connection of Installer’s Keypad.