Creating Potential Groups
Both bus refreshing modules and power feeding modules may be used to create a potential group. The base module
creates the possible isolation of the potential group on the left-hand side of the respective power distribution module.
It is not permitted for modules with 24 VDC and with 120/230 VAC field supply to be used in a joint potential group.
Therefore, when using digital input modules for 120/230 VAC, the power feeding module BL20-PF-120/230VAC-D is to be
used to create a special potential group.
C-rail (Cross Connection)
C-rails run through all I/O base modules. The C-rail for base modules for power distribution is mechanically separated; thus
potentially isolating the adjoining supply groups.
Access to the C-rail
Access to the C-rail is made via base modules with a C designation (i.e. BL20-S4T-SBCS). The corresponding connection
level is indicated by a thick black line on all base modules for BL20 I/O modules. For base modules for power distribution,
the black line is only above the connection “24" to indicate that the C-rail is separated from the adjoining potential group to
its left.
It is permitted to load the C-rail with a maximum of 24 V; never with 120/230 VAC.
Using the C-rail with Relay Modules
The C-rail may be used to supply a common voltage when relay modules are used. To accomplish this, the load voltage (24
VDC) is connected to a power distribution module and the base module BL20-P4x-SBBC with either tension clamp or screw
connections.
If the C-rail is used for the joint supply of voltage to relay modules, there must be a power distribution module used for the
potential isolation of the BL20 modules. The C-rail may still be used as protective earth (PE) once the potential isolation has
been made.
Using the C-rail as a Protective Earth
A C-rail may be used as a protective earth (PE), where the PE connection for each power distribution modules must be
connected to the mounting rail via an additional PE terminal, which is available as an accessory.