30 en | Troubleshooting Allegiant Keyboards
F.01U.127.290 | 2.0 | 2009.03 Instruction Manual Bosch Security Systems, Inc.
9 Troubleshooting
9.1 General
Problem Possible Causes
No Power Indication If powered from a non-modular type Allegiant, try another
keyboard port on the Allegiant. The port may have failed.
If powered from a modular type Allegiant, check the fuse on
main Allegiant power supply. Try another keyboard port.
If powered from a separate power source, check power source
or main AC supply of power source.
If power source is confirmed to be OK, the keyboard may have
an internal failure. Swap suspect keyboard with a known good
keyboard.
LED Displaying Flashing dashes If the login feature is enabled, the keyboard may be logged off.
(User LED lit and OFF LED lit)
If the login feature is not enabled, or the keyboard port is
logged in, there is likely a data communication error. Test the
keyboard cable in another keyboard port. Swap the suspect
keyboard with a known good keyboard. Try another keyboard
data cable. Check keyboard data cable connections.
If using RS-232 protocol models with a dial-up modem link, the
keyboard may be waiting for the operator to dial a phone
number and establish communication with the Allegiant.
Non-operating Key or LED Digit If a key does not seem to be working, verify that the attempted
function is applicable to the device being controlled, or the
switcher’s current situation.
Key or LED may be defective. Run the User Function 1 test
described in section below.