Access Control Interface Module System Overview | en 11
Bosch Security Systems, Inc. Installation and Operation Guide F.01U.215.244 | 05 | 2012.06
2.3 Basic features, displays, and reports
2.3.1 Basic features
Highly reliable and simple to use.
Provides direct interface to 26-bit Wiegand card readers.
Onboard buzzer output.
Card data LED indicator for card data when valid format is read.
Operational LED which indicates the CPU is functioning and unit is powered.
Onboard relay for switching 12/24 VDC/VAC power.
Option to unlock or lock door upon SDI bus failure.
Supervised Onboard point.
Request to Exit and Request to Enter inputs that can have a shunt only option.
Easily programmable entry and exit door strike and shunt control.
Four door states: Locked, Unlocked, Secured, Fire Unlock.
Disarm states using a token.
Pre-warn for holding door open too long.
Disarm system before or after a door opens.
Automatic Unlock door on disarm, Locked Door when armed.
Optional Deactivate strike when the door opened.
Interlock point assignment to prevent access until interlock point is normal.
999 Cards or Tokens.
Fourteen programmable levels of access authority.
Users can be added or deleted remotely, locally and with Command Center.
2.3.2 Displays and reports
Access Granted with user identification and user name.
No Entry with user identification and door user name.
Request to Enter with door point text.
Request to Exit with door point text.
Door Unlocked with door point text.
Door Locked with door point text.
Alarm Point ### with door point text.
Trouble Point ### with door point text.
Missing Point ### with door point text.
Please Close Door with door point text.
2.4 Materials Included
Bosch Security Systems ships the interface module in its own enclosure, or as a unit less
enclosure. You will receive the following parts with your package depending upon what model
is ordered.
–1 kΩ 1/2 watt end of line resistor.
Literature Pack containing: Operation and Installation Guide, Program Entry Guide,
Access Control Interface Module Program Record Sheet.
Hardware pack containing: three #6x3/8 self-tapping sheet metal screws to secure the
module on the mounting skirt or the enclosure.
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 31 32

Comentarios a estos manuales

Sin comentarios