20 en | Installation Access Control Interface Module
F.01U.215.244 | 05 | 2012.06 Installation and Operation Guide Bosch Security Systems, Inc.
Readers can be mounted up to 500 ft. (152 m) from the interface module. A typical reader
connection is shown in the illustration below.
Figure 3.5 D9210C Terminal
3.2.9 Setting the rotary switches and tagging the unit
The D9412GV4/D9412GV3/D9412GV2/D9412G/D9412 control panels support up to eight
door controllers. The D7412GV4/D7412GV3/D7412GV2/D7412G/D7412 control panel
supports up to two door controllers. Each interface module uses one of eight addresses.
Addresses cannot be duplicated. Because the interface module is always supervised, two
interface modules having the same address will not function correctly.
Terminal Description
COM The black wire provides the common for the reader. (Use this
terminal when comparing other reader voltages.
12 VDC The red wire is used to provide 12 VDC readers with power.
Current is limited only by the source providing the power.
5.2 VDC The orange wire is used to provide 5 VDC readers with power.
DATA 0 The green wire is the carrier of binary one (1) pulses from the
reader.
DATA 1 The white wire is the carrier of binary zero (0) pulses from the
reader.
BUZZER The yellow wire is the common for the reader buzzer or external
buzzer.
LED The brown wire is the common for the reader LED.
NOTICE!
LED Terminal can be used for the reader buzzer or common for the external buzzer.