| Approved Applications Compliance Guide | 5.0 Compatible UL Listed Components
16 Bosch Security Systems, Inc. | 3/12 | F01U266055-01
5.0 Compatible UL Listed Components
In Table 3, the text in the columns and rows for GV4 Series Control Panel have the following
meanings:
No = Not acceptable for this application
Req. = Required for this application
Opt. = Optional for this application.
[Empty box] = Not used for this application
Table 3: UL Listed Components Compatible with the GV4 Series Control Panels
Household Burglary
Household Fire
Household Fire/
Burglary Combined
Central Station
Burglary
Police Connected
Burglary
Local Burglary
Local Fire/Burglary
Combined
D9412GV4/D7412GV4
Local Fire
D9412GV4/D7412GV4
Local and Central
Station Fire Combined
D9412GV4/D7412GV4
Local and Central
Station Fire/ Burglary
D9412GV4/D7412GV4
Central Station Fire/
Burglary Combined
D9412GV4/D7412GV4
Central Station Fire
D9412GV4/D7412GV4
Electrically Actuated
Transmitte
r
D9412GV4/D7412GV4
Minimum Hours of Standby Battery 4 24 + 4 min alarm 4 4 4 24 + 5 min alarm
D8103/D8109 Enclosure Opt. Opt. Opt. Opt. No Opt. No Opt. Opt. No No Opt. No
D8108A Enclosure Opt. Opt. Opt. Opt. Req. Opt.. Req. Opt. Opt. Req. Req. Opt. Opt.
D125B Class B, Style A Powered Loop
Interface*
Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D129 Class A, Style D Initiating Module* Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D928 Dual Phone Line Module** Opt. Opt. Opt. Opt. Opt. Opt. Required if using two telephone lines for communication.
D192G Class “B”, Style Y Bell Circuit
Supervision
Opt. Opt. Opt. Opt. Opt. Opt. Req. Req. Req. Req. Req. Req.
D268/D269H Independent Zone Control Optional. Only connect to Zones 1 to 8. No No No No No No No
DS7432 Eight Input Remote Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
DS7457iF Single Zone Input Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
DS7560i Dual Zone Input Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
DS7461i Single Zone Input Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
DS7465i Input/Output Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
B208 Octo-input Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
B308 Octo-output Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
B420 Ethernet Communication Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
DX4020 Network Interface Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
ITS-DX4020-G Network Interface Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
B820 Inovonics Interface Module Opt. Opt. Opt. Opt. Opt. Opt. NA NA NA NA NA NA NA
D130 Relay Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D1255 and D1260 Keypads Opt. Opt. Opt. Opt. Opt. Opt. No No No No No No No
D1256 Command Center and D1257
Annunciator
Opt. Opt. Opt. Opt. Opt. Opt. No No No No No No No
D1255B and D1260B Keypads Opt. Opt. Opt. Opt. Opt. Opt. No No No No No No No
D1255RB, D1256RB, D1257RB No Opt. Opt. No No No Req. Req. Req. Req. Req. Req.
D1640 Transformer Required for all applications.
D8004 Transformer Enclosure Opt. Opt. Opt. Opt. Opt. Opt. Req. Req. Req. Req. Req. Req.
D8125 Class B, Style 4.0 POPEX Module Required for the D9127T/U POPITs.
D8125MUX Class B, Style 4.0 Required for MUX devices. Refer to Section 7.1 D8125MUX on page 22.
D9127T/U Class B, Style A POPIT Modules Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D8128D OctoPOPIT Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D8129 OctoRelay Optional. For remote annunciation of system functions.
D8130 Release Module Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D8132 Battery Charger
Refer to Table 7: Current Rating Chart for Standby
Battery Calculations
No No No No No No No
D9131A Parallel Printer Interface Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D9210C Access Control Interface** Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. Opt. No
* The D125B is required to connect two-wire fire alarm initiating devices. The D125B provides two powered loops for connecting listed two-wire smoke detectors.
The D129 provides two non-powered Class “A” initiating circuits.
** Applicable to the D9412GV4 and D7412GV4 Control Panels only.