GV4 Series | Approved Applications Compliance Guide | 2.0 Optional Compatible Equipment
Bosch Security Systems, Inc. | 3/12 | F01U266055-01 5
Bell Test at Arming: UL Standard 365
requires a Bell Test at arming for bank
safe and vault applications.
2.2.4 System Configuration Requirements
The following configuration and programming
options are required for UL Bank Safe and Vault
Systems. Refer to the
D9412GV4/D7412GV4/D7212GV4 Program Entry
Guide (P/N: F01U218312) for programming
information.
Safe and Vault Protective Circuits
To test the devices that protect the safe(s) or
vault(s) without sounding the bell, specify the
devices’ points as controlled zones and
supervised for trouble conditions. Refer to Point
Index in the D9412GV4/D7412GV4/D7212GV4
Program Entry Guide (P/N: F01U218312) for more
information.
Bell Configuration
UL 365 requires the bell time to be 15 to 30 min.
The Rothenbuhler 5110 Bell provides selectable
bell time through manipulation of its jumpers.
Refer to the manufacturer’s installation
instructions for more information.
In addition to the jumper settings inside the bell,
you can activate the control panel for a bell time
of 15 min.
UL 365 requires a Bell Test at arming and must
be enabled in control panel programming.
Refer to Bell Parameters in the
D9412GV4/D7412GV4/D7212GV4 Program Entry
Guide (P/N: F01U218312) for more bell time and
test programming information.
Bell Test
To enable the bell test feature, you enable an
unused area of the control panel. Enable the bell
test feature for the unused area only. Program
Relay B as the area bell relay for the unused area.
All pass codes with authority to arm the safe or
vault and also send a Closing Report must be
valid in this area. Program the area for a five-
second exit delay. Refer to Figure 1 on page 6 for
test connections. To complete the installation for
this feature, connect the output to a D133 Relay
Module.
2.2.5 Exit Delay
The control panel’s programmed maximum exit
delay must not exceed 30 sec.
2.2.6 Equipment Requirements
GV4 Series Control Panel
Two (2) D126 12 V, 7 Ah batteries
Two (2) D1218 12 V 18 Ah batteries
D8132 Battery Charger Module
Two (2) D8108A Enclosures
D122 Dual Battery Harness
D122L Dual Battery Harness
D133 Relay Module
EVD System (Listed Safe/Vault)
2.2.7 Wiring the Rothenbuhler 5110/4001-42
High Security Bell to the GV4 Series
Control Panel
Warning: Wear ear protection when
installing and testing the Rothenbuhler
High Security Bell.
Sound levels greater than 95 dBA at
3 m (10 ft) can occur.
1. Remove all power from the control panel.
2. Use six-conductor 1.2 mm (18 AWG) stranded
wire between the control panel and the 5110
Logic Board (located in the bell enclosure).
3. If you do not have a Silence switch,
temporarily install a 1 resistor across TB1-1
and TB1-6 on the 5110 Logic Board. The
resistor keeps the 5110’s bell silent during
the installation and alignment procedures.
Also place a temporary wire jumper across
the TB1-6 Bell Relay and TB1-7. Refer to
Figure 2 on page 7 for wiring a Silence switch.
4. Mount the D8108A’s 4001-42 External
Balanced Line Module and wire it to the 5110
Logic Board using two-conductor 0.8 mm (22
AWG) cable.
5. Wire the 4001-42 to the control panel. Refer
to Figure 2 and the Rothenbuhler installation
manual.
6. Before supplying AC and DC power to the
control panel and bell, ensure you are
wearing ear protection. The bell sounds for 2
sec and then silences during power up.