| Approved Applications Compliance Guide | 2.0 Optional Compatible Equipment
8 Bosch Security Systems, Inc. | 3/12 | F01U266055-01
UL requires that power outputs are
not shared between fire and non-
fire devices unless all devices are in
conduit within 20 ft and are in the
same room
(D9412GV4/D7412GV4).
2.3.1 Four-Wire Smoke Detectors
When using four-wire smoke detectors, install
a power supervision device according to the
manufacturer’s instructions. You can connect
any number of four-wire smoke detectors to
the GV4 Series Control Panels (subject to
available auxiliary power).
The Reset Sensor command is available from
the keypads when the Reset Sensor is enabled.
Connect the smoke detectors to a suitable
interface such as the D125B or D129, or to the
D9127 Modules when used with a GV4 Series
Control Panel. Smoke detectors can also be
connected to the on-board points to meet UL
and NFPA requirements.
When using four-wire smoke detectors, install
a power supervision unit according to the
manufacturer’s instructions. Refer to Section
2.3.5 Other Devices.
2.3.2 Two-Wire Smoke Detectors
Two-wire smoke detectors connect to the
control panel only through the D125B Powered
Loop Interface. Two-wire detectors must be
evaluated for electrical compatibility, and be
UL Listed for use with the control panel. Refer
to Table 1 on page 10 for the two-wire smoke
detectors that are UL Listed for compatibility
and the maximum number of detectors that
can be connected to each loop of the D125B
Powered Loop Interface Module.
You can also consult the smoke detector
manufacturer to determine if a particular
smoke detector is UL Listed for use with the
D9412GV4 and D7412GV4 Control Panels. The
Reset Sensor command is available from the
keypads when Reset Sensor is enabled.
2.3.3 Two-Wire Smoke Detector
Specifications
Voltage Range: 8.0 VDC to 14 VDC
UL Compatibility Identifier: Type A (for
control panel, detector, and base)
2.3.4 NFPA Style A (Class “B”) Circuit
Loops A and B on the D125B Module are NFPA
Style A (Class “B”) initiating circuits suitable
for connecting any fire alarm initiating device,
including two-wire and four-wire smoke
detectors. To connect initiating devices to on-
board points (1 through 8) on the GV4 Series
Control Panel:
Use a D125B Powered Loop Interface
Module with two-wire initiating devices for
a D9412GV4/D7412GV4/D7212GV4 Control
Panel).
Use a D129 Dual Class “A” (NFPA Style D)
Initiating Circuit Module with any type of
initiating device, except a two-wire smoke
detector.
Use the following guidelines when connecting
fire alarm initiating devices to off-board points:
Do not connect two-wire smoke detectors
to
POPITs or MUX bus inputs.
Use the D9127U or D9127T POPIT Modules
to connect four-wire smoke detectors when
using a GV4 Series Control Panel.
Consult the UL Listed Two-Wire
Smoke Detectors Compatible with the
D125B section 2.3.6 to determine
which product best fits your
application.
The control panel does not support
multiple detectors in alarm. The
control panel is intended to handle
detectors with optional features.
Detectors from different
manufacturers cannot be mixed on
the same circuit.
The expansion bus can be shared
between fire and non-fire devices
where the POPIT module is
providing data isolation between
the input and the bus connections
(D9412GV4/D7412GV4).