D9412GV3/D7412GV3 | Operation and Installation Guide | 4.0 Installation
.
Bosch Security Systems, Inc. | 2/10 | F01U143070-01 17
Caution: Do not use telephone or
electrical ground for the earth ground
connection. Use
1.8 mm (14 AWG) to 1.5 mm (16 AWG)
wire when making the connection.
Do not connect other control panel
terminals to earth ground.
4.5.2 Ground Fault Detect Enable
To meet UL 864 requirements, enable
Ground Fault Detect.
A ground fault is a circuit impedance to earth ground.
The control panel has a ground fault detection circuit
that, when enabled, detects ground faults on
Terminals 1 to 9 and 11 to 32. The control panel also
detects and annunciates ground faults on any device
connected to it.
If a ground fault condition occurs, the keypads display
SERVC GND FAULT and the control panel transmits
a GROUND FAULT TROUBLE, AREA 1.
When the control panel recognizes that the ground
fault condition is corrected, and remains corrected for
between 5 to 45 consecutive sec, a Restoral Report is
sent.
The D9412GV3 and D7412GV3 Control
Panels log and print a Ground Fault event
as a Trouble Point 256 if communicating
in Modem IIIa
2
format. If communicating
in Contact ID format, the control panels
generate a Ground Fault (310) event.
4.5.3 Enabling Ground Fault Detection
To enable Ground Fault Detect Enable, lock (close)
the S4 Ground Fault Detect Pin on the control panel
(Figure 3).
Figure 3: Enabling Ground Fault Detection
EARTH GROUND
COMMON
BA TT ER Y NEG AT IVE ONLY
BAT T ER Y POSITIVE ONLY
REL AY A
REL AY B
REL AY C
+ AUX POWER
CLAS S 2 TRAN SFORM ER
16.5 VAC 40 VA 60 Hz
Model D 1640
Int er nally Fused - Do not shor t
Requi res Unswitched Outlet
Do n ot shar e with ot he r equi pment
S4 GROUND FAU LT DETECT
Ena bl ed
Di s a bled
RED
ON when comm unicating
OFF when idl e
Co mmerci al Pr ot ect ed- Pr em is es Control Pa n el
D9412G V3 Control Pane l is UL Listed For Cen t r al Stat ion, Local , Aux iliar y, Propr i etary, and Househol d
Fi re Al arm, and Ce n t r al Stat ion, Local , Police St ation Co nnect, Househol d Burgl a r Al arm and Enc r yp t ed
Li ne Se c ur i ty whe n com m unicat ing via a net wor k.
System is intended to be checked by a Qualified Techni cian at least every 3 years.
Th e types of initiat ing ci rcui ts the cont rol pane l has been approved f or are A, M, W, SS.
Th e types of si gnaling the control panel has been appr oved for ar e DAC, OT, NC
VOLT A GE RANGES
O pen 3. 7 - 5. 0 V DC Short 0.0 - 1. 3 VDC
N orm al 2. 0 - 3. 0 VDC
Reset Pin
Disab le al l except Bat tery
Ch a r g ing an d P rogramming
PERI PHER AL DE VI CE CONNECTIONS
RED P OWER +
YEL L O W DATA BU S A
GREEN DATA BU S B
BL A C K C OMMON
ZON EX OUT 1
ZONEX IN 1
N. F .P. A.
St y le 4.0
Si g na ling
Li ne
Ci rcu its
F01U143074- 02
LE Ds O ff Wh en Normal
YE L LO W - C har gi ng St atus
RED - Low Batter y - 12.1 VDC
10. 2 VDC - Battery Loa d Shed
Thi s equi pment should be instal led in accor dance with the NFPA 70 (Nati onal Elect r ical Code) and
NF P A 72 (Nati onal Fire Alar m Code ) for Loca l , Ce n t ral St a ti on, Pr opr iet ary and H ous ehold Fire Warning
Sys t e ms and under the limits of the Local Authority Having Jur isdi cti on (National Fi re Prot ec tion
As s o ciation, Ba t t e rmarch Par k, Qui ncy, M A 02269). Pr int ed inf ormation desc ribing
pr o per instal lat ion,
oper at ion, testing, mai nt enance, evacu ation pl anning and repai r service is t obe provi ded with this
equi pmen t.
D9412GV3
26
25
ZO NEX POWER +
24
ZO NEX COMMON
23
PHONE L INE SEIZED LED
TIP
RING
TELCO CORD MODEL D161
SDI Conn ect or
ZON EX OUT 2
ZONEX IN 2
Refer to the D9 4 1 2 GV3/D 7412G V3 Ap proved App lication s Complian ce Guide (P/N: F01U 143069)
for Sy stem W iri ng Diagram, Iss ue A an d f or compat ible sm oke det ect or s.
PO W ER SUPP LY REQUIREMENTS
The Power Su pp l y provide s a m axi mum of 1. 4 Amps for the Control Panel an d al l
A ccesso ry Device s. For Syst em L oadi ng, refer to the D 9412G V3/ D74 12GV3 O perat ion
an d Installat i on Gui de (P/N: F0 1U1430 70).
( P/ N: F01U1 43070) for Power Re qui remen ts relat ing to Terminals 6 an d 7 .
CA UTION:
Re f e r to the D 9412G V3/ D741 2GV3 Operation an d Installat i on Gui de
All external conn ect ion s exc e pt Ter m i nal 5 (battery positive) are i nhe r ent l y power
limited. Re quirem en ts f or ba ttery stan dby time mi ght r ed uce allowable ou tput.
WARNI NG!
Mu lti-Ba tte ry in stallat i on re qu ires
Mo de l D 122/ D 122 L Du al Ba ttery
H ar n ess . Impro per installation can
be a fire h azard .
B at t er y: R epl ac e every 3 to
5 years with one or tw o Mod el
D126 or D1218 12V Le ad Acid
B at t er i es.
Inco rrect wiring will
dam age this equi pm ent .
PR OGRAMMABLE
ALARM OUTPUTS
Ter m inal s
SW I TCH ED AUX
and6
7
Ter minal 8
Oper at ion Moni tor LED
Pulses when No r m a l
Flickers when Ri n g ing
GREEN
D5200/D5360
PRO G CONN
Po int 8, S3 Option
Cl o se d = 1 k
Ω
EO L
No r mal Operat ion
Open =AB- 12 UL
Be l l Box 220 k
Ω
25
Poi nt 3Point 4
161514
Point 1 Poi nt 2
1211 13
Poi nt 5Point 6
1817 19
Point 7 Poi nt 8
21
20
22
Suitabl e for dr y ind oor
use only.
Devi ces pow ered by the
AUX power output must
be supervised.
Mini mum syst em req uirement s for Cl assificat ion in accor dance with AN S I/SIA CP -01- 2000:
UL L ist ed and Cl assified cont rol uni t Model D9412GV3, D7412G V3, or D7212G V3;
UL L ist ed and Cl assified keypad Model D1256, D1257, D1260, D1255, D 1255R, or D1255RW;
UL L ist ed Local Bell
WARNING !
To pr ev en t risk of
el ect ri c shock,
di sconn ect AC po wer
and t el ephon e lines
before servicing .
CA UT I ON: Avoi d dam a ge to Panel.
Do n ot connect 24 V to terminals.
Max imum ch arging cu rrent 1.4 A
Re set Pi n
Disab le Al l Ex c ept Battery
Charging A nd Prog rammi ng
27
PR OG
CONN
26
25
24
Re se t Pi n
Disab le Al l Ex c ep t Battery
Ch a r g ing A nd Prog ram m i ng
27
PRO G
CO NN
26
25
24
2
1
1 - S4 Locked (Closed). Control panels detects
ground faults.
2 - S4 Unlocked (Open). Control panel does not
detect ground faults.
4.5.4 Ground Fault Specifications
Table 6 provides the impedance specifications for
detecting ground faults when any terminal or field
wiring is shorted to ground.
Table 6: Ground Fault Impedance
Specifications
Impedance Control Panel Detects Ground Fault
300
Yes
300 to
200 k
Detection depends upon the terminal
200 k
No
4.5.5 Locking the Reset Pin
Locking the reset pin disables the control panel
(Figure 4). When the control panel is disabled, the
system ignores the keypads and points. CALL FOR
SERVICE appears in keypad displays when the pin is
locked down.
On-board relays (Terminals 6 and 7) and off-board
relays deactivate when the control panel is reset.
Terminal 8 has power when the relay is deactivated.
Activation interrupts power at that terminal. The on-
board relay (Terminal 8) remains deactivated when
the reset pin is locked in the disable position.
Releasing the reset pin from the closed position
resets the control panel. The control panel resets all
its timers, counters, indexes, and buffers. Any points
that restore after a reset do not generate Restoral
Reports.