D9412GV3/D7412GV3 | Operation and Installation Guide | 10.0 Off-Board Relays
.
Bosch Security Systems, Inc. | 2/10 | F01U143070-01 55
10.2.2 Installation
Install the D811 in the enclosure with the control
panel (Figure 25) or in an adjacent enclosure no more
than
1.5 m (5 ft.) from the control panel. Use 1.5 mm
(16 AWG) to 0.8 mm (22 AWG) wire.
To install D811 Modules in the enclosure with the
control panel:
1. Align the D811 Module with any of the four
mounting locations in the enclosure (Figure 2 on
page 16).
2. Using the screws provided with the module,
secure it in the enclosure.
Use the D137 Mounting Bracket or D9002
Mounting Skirt to install D811 Modules in
enclosures with no available module mounting
locations.
10.2.3 Wiring Connections
Power down the control panel to connect D811
Modules as shown in Figure 25 on this page and
Figure 26 on page 56.
The D811 for Relay 53 connects to
Zonex 1.
The D811 for Relay 117 connects to
Zonex 2 on the D9412GV3.
Figure 25: D811 Module Wiring to the D9412GV3
GND
AUX
DATA
GN D
AUX
DATA
3
2
1
21 22
R eset Pin
Disable all except Battery
Charging and Progr amming
PERIPHE RAL DEVICE CO NNE CTIONS
RED POWER +
YELLOW
DATA BUS A
GREE N DATA BUS B
BLACK COMM ON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 4.0
Signaling
Line
Circu its
26
ZONEX POWER +
24
ZONEX COMMON
23
ZONEX OUT 2
ZONEX IN 2
Op era t i on Monitor LED
Pulses when Norm al
Flickers when Rin ging
GRE EN
D5200/D5360
PROG CONN
Point 8 , S3 Option
Closed = 1 k
Ω
EOL
Norm al Operation
Op en =A B - 12 UL
Bell Bo x 220 k
Ω
25
5
5
25
1 - D811 for Relay 53
2- D811 for Relay 117
3- On-board points