D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0 Off-Board Points
48 Bosch Security Systems, Inc. | 2/10 | F01U143070-01
Figure 19: Connecting D8128D OctoPOPITs to the D9412GV3
21 22
Reset Pin
Disable all except Battery
Charging and Programming
PERIPHERAL DEVICE CON NECTIONS
RED POWER +
YELLOW
DATA BUS A
G REEN DATA BUS B
BLACK COMMON
ZO N E X OUT 1
ZONEX IN 1
N.F.P.A.
St yle 4.0
Signaling
Line
Circuits
26
ZONEX POWER +
24
ZO NE X COM MO N
23
ZONEX OUT 2
ZO NEX IN 2
Op erat io n M o nit o r L ED
Pu lse s whe n No rm al
Flick er s when Ringin g
GRE EN
D5 200 /D5 360
PRO G CONN
Poi nt 8, S3 Opt ion
Clos ed = 1 k
Ω
EOL
N or mal Ope r ati on
Op en = AB-1 2 UL
Bel l Bo x 2 20 k
Ω
25
12
1
5
2
3
2
4
6 6
7
8
9
8
6
6
11
10
25
1 - Zonex Bus 1, Switch 1 ON (Points 9 to 72)
2 - Bus 1
3 - First address on Zonex Bus 1
4 - Last address on Zonex Bus 1
5 - Zonex Bus 1, Switch 1 OFF (Points 73 to 127)
6 - Sensor loops
7 - Zonex Bus 2, Switch 1 ON (Points 129 to 192)
8 - Bus 2
9 - First address on Zonex Bus 2
10 - Last address on Zonex Bus 2
11 - Zonex Bus 2, Switch 1 OFF (Points 193 to
240)
12 - On-board points
Refer to Address Switches in Section 9.4.4 Setting the OctoPOPIT Switches on page 46 for
information about making these switch settings. Refer to Table 16 on page 46 for information
about setting Switch 5.
For system supervision, do not use looped wire terminals. Break the wire run to provide
supervision of the connections.