Bosch D9000, G Guía de usuario Pagina 9

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 39
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 8
Galaxy Interface Manual for Bosch G-series Alarm Panels
Page 9 of 39
1.3.3 BOSH GV4 NETWORK REQUIREMENTS
BOSH B420 ETHERNET MODULE SETTINGS:
UsetheseknownEthernetandcommunicationsettingsfortheB420module(GV4)when
interfacingwithSystemGalaxy.
1. TheB420Moduledefaultport#is7700.Galaxydoes notrecommendchangingthisvalue.
2. TheBoschrequiresadedicatedB420Moduleforeachcommchannel.ThereforeadedicatedB420
moduleisrequiredforSystemGalaxy.
3. TheB420Modulemusthave‘Automation’enabled.Thisisdon ebysettingtheB420’sRotarySwitch
toauni
queandvalidvalue(1,2,or3).SeethechartontheB420InstallGuide(PN:FOU1O215236/7).
4. YoucanusetheBOSCHRPSsoftwaretosetuptheEthernet/communicationsettings.
» TheRPGSoftwarerequiresitsUSBdongletobei
nstalledinthePCinordertooperate.
5. (GV4)YoumustconfigurethePacketControlsettingsoftheB420tocommunicatewithSystem
Galaxy.ThisisdoneviatheB420WebConfigurationPage
.
» Toaccessthewebpage,youmustsettheB420RotarySwitchto‘0’andthenpowerfailthe
B420(toinitializethe‘0’address).Youmustalsoknowtheunit’sIPaddressinordertoopen
thewebpageinabrowser.UnderChannel1 > SerialSettings:
EnablePa
ckingmustbe‘checked’
IdleGapTimemustbe“12msec”
FlushModeInput&OutputBuffersmustallbesettoYES
6. YoumustreturntheRotarySwitchtoasettingvalueforautomationafterconfiguringthePacket
Controlsettings.AgainyoumustpowerfailtheB420toreinitializetheaddresstothecorrectvalue.
Vista de pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 38 39

Comentarios a estos manuales

Sin comentarios