© Radionics Inc. reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.
18
DS7400Xi Version 3.04
2) Multiplex Smoke Detectors (V3.04)
The DS7400Xi has the capacity to use
Detection Systems MX280 Series Multiplex Smoke Detectors.
These Low Profile Smoke Detectors mount directly to the Multiplex Bus
and have the ability to self monitor the sensitivity of the detector using
the ChamberCheck feature.
When a smoke detector is out of its sensitivity range, the keypads
display “Dirty Chamber,” and the panel may be programmed to send a
Dirty Chamber report to the Central Station.
The MX280THL Smoke Detector also has the ability to send a Low
Temperature (“Freeze Alarm”) report when the temperature in the
building is less than 45 degrees F for 30 minutes or more.
The MX280 Series Smoke Detectors became available during 1998.
DS7400Xi Panel Wiring & Programming