Programming Zones:
Data Digit 1
DS7400Xi Panel Wiring & Programming
MX280, MX280TH
Multiplex Smoke Detectors
3
For Mux Smoke Detector zones,
use a Zone Function programmed
as a Fire Zone [with or without
verification] with Trouble on Open
Data Digit 2
MX280THL Mux Smoke
Detectors w LowTemp Alarm
4
For Mux Smoke Det [odd-numbered]
zones, use Zn Function programmed
as Fire Zone with Trouble on Open
For Mux Smoke Det Lo Temp Alarm [even-numbered]
zones, use Zone Function programmed as
Supervisory Zone with Trouble on Open
Data Digit 2
Data
Digit
1