Addressing a Multiplex Sensor
DS7400Xi Panel Wiring & Programming
Must be done prior to installation of the device
Program Zone.
Address 0026-0145 must be programmed before addressing sensor.
Disconnect the multiplex bus. Only one device (the one being addressed)
should be connected to the bus at this time
If using BUSLOC, program BUSLOC code
BusLoc code (address 9999) is a special anti-takeover code that is
programmed into the sensors
BusLoc code in panel must match BusLoc code in sensors; control can’t
be replaced using these sensors unless you know BusLoc code.
Enter multiplex programming mode. Enter Address 9995.
Connect sensors one at a time, and follow instructions on LCD.