DS7400XiV4-EXP | Reference Guide | 7. Reference Materials EN | 113
Bosch Security Systems | 1/05| 4998154963B
Water Flow Zone: This is a zone programmed to
operate like a Fire Zone, but is specifically intended for
water flow switches.
An optional retard timer can be programmed to
compensate for changes in water pressure. If the
timer is used, the water flow zone must be activated
for the complete time period; an alarm will be
initiated at the end of the timer period.
The maximum combined water flow delay of the
control panel and the device must not exceed two
minutes.
Any zone can be a water flow zone, but
only zones 1 through 4 may be
programmed as delayed water flow zones.
Supervisory Zone: This is a zone programmed to
accommodate shut-off valves.
It will indicate a supervisory condition at the
keypads when activated.
7.2.3 Zone Programming
Zone: A Zone is an input to the DS7400Xi
Control/Communicator.
There are eight hardwired zones on the main circuit
board.
Additional zones may be added by using the
DS7433 (8 zone expansion module), the DS7430
(multiplex loop module), and/or other modules.
Single Zone Input: This is an individual zone such as
the on-board zones and multiplex contact zones.
Multiple Zone Input: This is a zone connected to one
of the 8-Input Modules (DS7432E or DS7433) or to a
Dual Zone Module (DS7460i).
The inputs are programmed separately (see the
separate Programming Addresses Worksheet, P/N:
29802).
When using the Dual Zone Module (DS7460), loop
A is always programmed as an odd numbered
program address (ending in 1, 3, 5, 7, or 9). Loop B
is the even numbered program address that follows
loop A.
DS7465i: This is the input zone or the output relay on a
DS7465i. The odd numbered zone is programmed for
the input zone function and the even numbered zone is
programmed for the output function.
Multiplex Smoke: This is a multiplexed input zone
(zones 9-248) that is used with a MX250 or MX280
series smoke detector. This zone must have a Zone
Function of Fire Zone and Trouble on Open applied
to the multiplex smoke zone.
Smoke alarm: This must be the odd-numbered zone
of the zone pair required for these devices. The zone
must be programmed with a zone function that is set
for Fire Zone and Trouble on Open.
7.2.4 Output Programming
Latch on Any Zone Alarm: This is an output
programmed to activate upon any zone alarm
(including invisible zones) and will latch until the
system has been disarmed.
If this output is programmed to respond only to a
fire zone, it will remain latched until the fire reset
command is performed.
ON during Entry Pre-Alert: This is an output
programmed to activate when an entry/exit zone is
violated while the system is armed.
It will remain activated until the system is
disarmed, or until the entry delay time has
expired.
ON for 10 seconds after [PIN][System Reset] is
entered: This is an output programmed to activate for
10 seconds after the fire reset command is entered at
the keypad or if a Fire Zone with Verification
activates.
This output is intended to be used to power 4-wire
smoke detectors or any other device that requires
a power interruption to reset an alarm condition.
When Programmable Output 2 is
programmed this way, it will normally
supply auxiliary power and will turn OFF for
10 seconds when the fire reset command
is entered.
ON when System is Armed: This is an output
programmed to activate when the system is armed.
It will remain activated until the system is
disarmed.