Vista de pagina 13
with requirements in NEC code and as recommended
by manufacturer for type of line being protected.
C. Interference Protection: Components shall be
unaffected by radiated RFI and electrical
induction of 15V/m over a frequency range of 10
to 10,000 MHz and conducted interference signals
up to 0.25-V RMS injected into power supply lines
at 10 to 10,000 MHz.
D. Tamper Protection: Tamper switches on detection
devices, control units, annunciators, and other
system components shall initiate a tamper-alarm
signal when unit is opened or partially
disassembled and when entering conductors are cut
or disconnected. Central-station control-unit
alarm display shall identify tamper alarms and
indicate locations.
E. Self-Testing Devices: Automatically test
themselves periodically, but not less than once
per hour, to verify normal device functioning and
alarm initiation capability. Devices transmit
test failure to central-station control unit.
F. Anti-masking Devices: Automatically check
operation continuously or at intervals of a
minute or less, and use signal-processing logic
to detect blocking, masking, jamming, tampering,
or other operational dysfunction. Devices
transmit detection of operational dysfunction to
central-station control unit as an alarm signal.
G. Addressable Devices: Transmitter and receivers
shall communicate unique device identification
and status reports to central-station control
unit.
2.3 ENCLOSURES
A. Interior Sensors: Enclosures that protect
against dust, falling dirt, and dripping non-
corrosive liquids.
B. Interior Electronics: NEMA 250, Type 12.
Vista de pagina 13