g. Test each initiating and indicating
device for alarm operation and proper
response at control unit.
h. Test both primary and secondary power.
Verify, by test, that UPS is capable of
operating the system for period and in
manner specified.
D. Report of Tests and Inspections: Prepare a
written record of tests, inspections, and
detailed test results in the form of a test log.
E. Tag all equipment, stations, and other components
for which tests have been satisfactorily
completed.
3.5 DEMONSTRATION & TRAINING
A. Integrated Access Control System training shall
include two sessions arranged with the owner at
least one week prior to the training dates.
Training manuals shall be delivered for each
trainee with an additional one copy delivered for
archiving on the project site. Duration of the
training classes shall be a minimum of two (2)
hours.
B. Training manuals shall consist of an agenda,
defined objectives for each lesion, system and
sub-system with a detailed description of the
subject matter of each lesson, and the
manufacturer’s written operation and system
manuals. At a minimum, training agenda shall
consist of the following:
1. An overview of the system components and
features.
2. A detailed description of how the system
will operate to meet the performance
requirements of the access control system.
3. Startup and orderly shutdown and reset
procedures for the system.
4. Hands on training on all integrated access
components, features and functions.
5. A complete description of Door Management
Alarm (DMA) capabilities and limitations.