Control PanelsB5512/B4512 en UL Installation Instructions
P1P1P1OUTPUT A (C terminal) = AUX PWRCOM AUXOUTPUT A (C terminal) = COMOUTPUT A (C terminal) = DRYCOM AUXCOM AUXCOM AUXP1TMPR1 COM 2 7
Using interconnect wiringInterconnect wiring connectors parallel the SDI2 PWR, A, B, and COM terminals on theterminal strip. In installations with mul
Install the transformer!Caution!Do not short-circuit the terminals of the transformer: Shorting the terminals opens the inter-nal fuse, causing perman
3. Connect the black battery lead to the BAT- terminal, and then to the negative (-) side ofthe battery.4. Connect the red battery lead to the BAT+ te
Callout ᅳ Description6 ᅳ 12 V sealed lead-acid rechargeable battery (D126/D1218)7 ᅳ Sensor loop wires Charge the batteryConnect the battery and then t
Recharge cycleAC ON - Battery charging begins and AC Restoral Reports sent.13.4 V - Battery Restoral Report sent. Battery float charged. Further infor
Installation and control panel wiring (B520)The power supply draws approximately 15 mA (+/- 1 mA) from the control panel.Ensure that there is enough p
Wire to the control panelWhen wiring a module to a control panel, use the terminal strip labeled with PWR, A, B, andCOM for SDI2 IN to wire to termina
Callout ᅳ Description1 ᅳ B520 Auxiliary Power Supply Module2 ᅳ Powered device (SDI2 module)3 ᅳ Terminal strip wiring4 ᅳ Interconnect wiring (P/N: F01U
iNotice!UL requires any device powered from a power output to be supervised. Total available powerThe control panel produces up to 800 mA of combined
N/O 1COMM 1N/C 1X1 +X1 -COMM 2N/O 2N/C 2X2 +X2 -21TMPR1 COM 2 7 COM 83 COM 4 5 COM 6RESETETHERNETCOM AUX R Y G BP
Callout ᅳ Description Callout ᅳ Description6 ᅳ Yellow LINK LED 16 ᅳ SDI2 terminals (power and data)7 ᅳ Plug-in module retention clip 17 ᅳ Auxiliary po
N/O 1COMMN/C 1X1 +X1 -COMMN/O 2N/C 2X2 +X2 -EOL14563297814101113+12TMPR1 COM 2 7 COM 83 COM 4 5 COM 6RESETETHERNETCOM AUX R
Battery lead supervision wiring1BAT 2-BAT 2+BAT 1-BAT 1+CHGR-VAUX+SUPVCHGR+243TMPR1 COM 2 7 COM 83 COM 4 5 COM 6RESETETHERNETC
43AUX PWRALARM TRIGCOMSUPV INALARM CKTGND OUTP1217 COM 8COUTPUTBUSBETHERNET100BASE-TLINKCOMMUNICATION MODULE 11 k End of Line ResistorsVol
Keyswitch wiring2345345671Figure 7.4: Keyswitch wiringCallout ᅳ Description1 ᅳ Maintained keyswitch2 ᅳ Momentary keyswitch3 ᅳ Common4 ᅳ Point input5 ᅳ
SDI2 devices general system wiring1 21664253TMPR1 COM 2 7 COM 83 COM 4 5 COM 6RESETETHERNETCOM AUX R Y G BPWR A
You can configure modules via home run, daisy chain, or single level T-tap anywhere on theSDI2 bus.2 2 2322 22422252 21TMPR1 COM 2 7 COM 8
Maximum cable lengthsThe following rules must be followed when wiring the SDI2 bus.– The SDI2 bus requires the use of un-shielded cable from 12 AWG t
AWG MFG/PN CapacitancepF/ftResistanceΩ/1000 ftMax Run NEC Type Definition16 BeldenHC275819.9 4.0 7000 Belden520223.5 4.2 5800 12 Belden500232 1.
Table of contents1Introduction 41.1 About documentation 41.1.1 Related documentation 41.2 Bosch Security Systems, Inc. product manufacturing dates 52S
Wiring label 7.6 30 en | Introduction Control Panels2013.01 | 04 | F01U265448 UL Installation Instructions
Specifications Control panel power supply specificationsVoltage Input (PowerSupply)Primary 18 VACterminals18 VAC 22 VA Class 2 transformer (CX4010)Sec
Point Thresholds On-board points1 to 8Open - 3.7 to 5.0 VDCNormal - 2.0 to 3.0 VDCShort - 0.0 to 1.3 VDCShort circuit current - 5 mACompatibleEnclosur
OUTPUT B Output B 22 AWG min (up to 12 AWG max)OUTPUT C Output CControl Panels Introduction | en 33 UL Installation Instructions 2013.01 | 04 | F01U2
Bosch Security Systems, Inc.130 Perinton ParkwayFairport, NY 14450USAwww.boschsecurity.com© Bosch Security Systems, Inc., 2013
IntroductionAbout documentationThis document contains instructions for a trained installer to properly install, configure, andoperate this control pan
7. Under Search Results, click the desired product. The product page opens with theDocuments tab selected.8. Click en to the right of the desired docu
System overviewB430Plug-in Tephone Communicator provides a single telephone RJ-45 connector to allow communication over telephone lines. ControlPanelO
Control panel installationInstall the enclosure and wiring labelRefer to Enclosures to determine if the application requires a specific enclosure.To i
Figure 3.2: B10 and B11 control panel placement locations1 ᅳ B10 Medium Control Panel Enclosure2 ᅳ B11 Small Control Panel Enclosure3 ᅳ Mounting clip
Connect earth groundTo help prevent damage from electrostatic discharges or other transient electrical surges,connect the system to earth ground at th