Battery lead supervision wiring
1
BAT 2-
BAT 2+
BAT 1-
BAT 1+
CHGR-
VAUX+
SUPV
CHGR+
2
4
3
TMPR
1 COM 2 7 COM 83 COM 4 5 COM 6
RESET
ETHERNET
COM AUX
R Y G B
PWR A B COM
+ BAT -
18VAC
B C
OUTPUT
NO C NC
OUTPUT A
7 COM 8
C
OUTPUT
B
USB
ETHERNET
100BASE-T
LINK
COMMUNICATION MODULE 1
1 k End of Line Resistors
Voltage Ranges
ON-BOARD POINTS
3.7 - 5.0 VDC
2.0 - 3.0 VDC
0.0 - 13 VDC
Open
Normal
Short
3 COM 4 5 COM 61 COM 2
R Y G B
SDI2
Device Bus
18 VAC
BATTERY OUTPUT A
AUX
- 12 V +
OUTPUT A
OUTPUT A
Jumper Under Cover
AUX PWR
COM
DRY
Figure 7.2: Battery supervision wiring
Callout Description
1 D113 Battery Lead Supervision Module, if required
2 Batteries
3 To supervision point
4 Control panel
Notification appliance circuit wiring
The control panels do not have an onboard NAC.
Programming determines the format of the output and the conditions that activate it. One self-
resetting circuit breaker protects against shorts. When using the relay to activate notification
appliance circuits in UL Listed fire alarm applications, install a D192G Notification Appliance
Circuit module.
Refer to the D192G Notification Appliance Circuit Module Installation Guide (P/N: 4998122260)
for detailed wiring information and specifications.
7.2
7.3
Control Panels Introduction | en 23
UL Installation Instructions 2013.01 | 04 | F01U265448