3. Connect the black battery lead to the BAT- terminal, and then to the negative (-) side of
the battery.
4. Connect the red battery lead to the BAT+ terminal, and then to the positive (+) side of the
battery.
Warning!
High current arcs are possible. The positive (red) battery lead and the BAT+ terminal can cre-
ate high current arcs if shorted to other terminals or the enclosure. Use caution when working
with the positive lead and BAT+. Always disconnect the positive (red) lead from the battery
before removing it from BAT+.
!
Caution!
The battery terminals and wire are not power limited. A 0.250 in (6.4 mm) space must be
maintained between the battery terminals, battery wiring, and all other wiring. Battery wiring
cannot share the same conduit, conduit fittings, or conduit knockouts with other wiring.
1
2
3
4
5
6
7
TMPR
1 COM 2 7 COM 83 COM 4 5 COM 6
RESET
ETHERNET
COM AUX
R Y G B
PWR A B COM
+ BAT -
18VAC
B C
OUTPUT
NO C NC
OUTPUT A
7 COM 8
C
OUTPUT
B
USB
ETHERNET
100BASE-T
LINK
COMMUNICATION MODULE 1
1 k End of Line Resistors
Voltage Ranges
ON-BOARD POINTS
3.7 - 5.0 VDC
2.0 - 3.0 VDC
0.0 - 13 VDC
Open
Normal
Short
3 COM 4 5 COM 61 COM 2
R Y G B
SDI2
Device Bus
18 VAC
BATTERY OUTPUT A
AUX
- 12 V +
OUTPUT A
OUTPUT A
Jumper Under Cover
AUX PWR
COM
DRY
Figure 4.1: Non-power-limited wiring
Callout Description
1 Conduit required for use with external batteries
2 To CX4010 UL Listed Class 2 Transformer 18 VAC 22 VA 60 Hz
3 0.25 in (6.4 mm) minimum
4 Battery terminals. BAT- is non-power limited
5 Battery wires
Control Panels Introduction | en 13
UL Installation Instructions 2013.01 | 04 | F01U265448