Point Thresholds On-board points
1 to 8
Open - 3.7 to 5.0 VDC
Normal - 2.0 to 3.0 VDC
Short - 0.0 to 1.3 VDC
Short circuit current - 5 mA
Compatible
Enclosures
B10 Medium Control Panel Enclosure, B11 Small Control Panel Enclosure, D2203
Enclosure, D8103 Universal Enclosure, D8108A Attack Resistant Enclosure, and
D8109 Fire Enclosure
Wire requirements
Terminal label Terminal description Requirements
18VAC AC 18 AWG min (up to 12 AWG max)
Earth ground 16 AWG min (up to 14 AWG max)
BAT + Battery + Bosch supplied wire lead, included with control
panel.
BAT - Battery - Bosch supplied wire lead, included with control
panel.
OUTPUT A NO Output A normally open 22 AWG min (up to 12 AWG max)
OUTPUT A C Output A common
OUTPUT A NC Output A normally closed
COM Common
AUX + AUX power
PWR/R SDI2 power 22 AWG min (up to 12 AWG max)
A/Y SDI2 data bus A 22 AWG min (up to 12 AWG max)
B/G SDI2 data bus B 22 AWG min (up to 12 AWG max)
COM/B SDI2 common 22 AWG min (up to 12 AWG max)
1 Point 1 22 AWG min (up to 12 AWG max)
COM Point 1/2 common
2 Point 2
3 Point 3
COM Point 3/4 common
4 Point 4
5 Point 5
COM Point 5/6 common
6 Point 6
7 Point 7
COM Point 7/8 common
8 Point 8
8.1
32 en | Introduction Control Panels
2013.01 | 04 | F01U265448 UL Installation Instructions