Callout Description
1 B520 Auxiliary Power Supply Module
2 Powered device (SDI2 module)
3 Terminal strip wiring
4 Interconnect wiring (P/N: F01U079745)
Wire to batteries
Wiring the B520 to BATT 1 is required for proper operation of standby power for the B520
module. Wiring the second battery (BATT 2) is optional. If a control panel is configured for two
batteries as the standby power source, then BATT 2 is also required for proper operation.
BATT 2 must have the same capacity and rating as BATT 1. Maximum standby power cannot
exceed 36 Ah.
BATT 1
BATT 2
R
B
R B
+ -
1
23
+ -
Figure 4.6: B520 BATT terminals wiring
Callout Description
1 Module
2 Battery 2 (BATT 2) - (12 V nominal lead acid)
3 Battery 1 (BATT 1) - (12 V nominal lead acid))
On-board outputs
Powered outputs
Circuit protection
Three self-resetting circuit breakers protect the control panel from short circuits on the
continuous and programmable power outputs.
If programmed for power supervision, the control panel adds a missing battery event to the
event log. If programmed for battery fault reports, the control panel sends a BATTERY
MISSING report in the Modem4 communication format, or Control Panel Battery Missing (311)
report in the Contact ID format.
One self-resetting circuit breaker protects the AUX (auxiliary power) terminal.
Another self-resetting circuit breaker protects the OUTPUT A’s C terminal.
The third self-resetting circuit breaker protects PWR/R terminal (power) of the SDI2 terminal
block.
5
5.1
5.1.1
18 en | Introduction Control Panels
2013.01 | 04 | F01U265448 UL Installation Instructions