D7212GV2 | Operation and Installation Guide | 4.0 Installation
16 Bosch Security Systems, Inc. | 2/07 | F01U003805-02
4.5.3 Enabling Ground Fault Detection
To enable the Ground Fault Detect Enable feature:
1. Lock (close) the S4 Ground Fault Detect Pin on the
control panel (Figure 4).
If your control panel has Version 7.02
firmware or earlier, you must do Step 2.
2. Program the Area 5 Silent Alarm Relay to a non-
zero value (1 to 128).
In remote programming software (RPS), the Area 5
Silent Alarm Relay is located in RELAY
PARAMETERS, Area Wide Relays, and Silent
Alarm Area 5 (Figure 5).
Figure 4: Ground Fault Detect (S4)
EARTH GROUND
COMM ON
RELAY A
RELAY B
RELAY C
+ AUX POWER
CLASS 2 TR ANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do not short
Requires Unswitched Outlet
Do not share with other equipment
GROUND FAULT DETECT
Enabled
Disabled
Digital Alarm Communicator Transmitter
D7212GV2 Control Panel is UL Listed for Household Fire Alarm, and Central Station, Local,
Pol ice Stati on Conn ect, House hold Bu rglar Al arm and En crypted Line Se curity w hen
com municati ng via a net work.
System is Intended To Be Checked By A Qualified Technician At Least Every 3 Years.
The types of initiating circuits for which the control panel has been approved are A, M, W, SS.
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW DATA BUS A
GR EEN D ATA BUS B
BLACK COMM ON
ZON EX OU T 1
ZONEX IN 1
N.F.P.A.
Style 4.0
Signali ng
Line
Circuits
F01U003800-01
1211 13
Point 1
Poi nt 2
1514 16
Point 3
Poi nt 4
1817 19
Poi nt 5
Point 6
2120 22
Poi nt 7
Point 8
LEDs Off When Normal
Charging Status
Low Battery - 12.1 VDC
YEL
RED
10.2 VDC - Battery Load Shed
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)
and NFPA 72 (National Fire Alarm Code) for Local, Central Station, Remote Station, Proprietary and
Household Fire Warning Systems and under the limits of the Local Authority Having Jurisdiction
(National Fire Protection Association, Battermarch Park, Quincy, MA 02269). Printed information
describing proper installation, operation, testing, maintenance, evacuation planning and repair
service is to be provided with this equipment.
D7212GV2
NOT USED
26
25
NOT USED
ZONEX POW ER +
24
ZONEX COMMON
23
SDI Connector
Refer to
D7212GV2 Approved Applications Compliance Guide
(P/N: F01U003806)
For System Wiring Diagram, Issue A and for Compatible Smoke Detectors
BATTERY NEGATIVE ONLY
BATTERY POSITIVE ONLY
CAUTION:
Avoid damage to Panel.
Do not connect 24 V to terminals.
Maximum charging current 1.4 A
PHONE
LED
RED
ON when
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO CORD
MODEL D161
CAUTION:
Ref er to
D7212GV2 Operation and Installation Guide
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and al l
Accessory Devices. For System Loading, refer to
D7212GV2 Operation and
Installation Guide
(P/N: F01U003805).
All external connections except Terminal 5 (battery positive) are inherently power
limited. Requirements for battery standby time might reduce allowable output.
(P/N: F01U003805) for Power Requirements relating to Terminals 6 and 7 .
WARNING!
Multi-B attery ins tallation requires
Model D122/D122L Dual Battery
Harness. Improper installation can
be a fire hazard.
Battery: Replace every 3 to
5 years with one or two Model
D126 or D1218 12V Lead Acid
Batteries.
GRN
Point 8
S3 Option
Closed = 1K
W
EOL
Normal Operation
Open =AB- 12 UL
Bell Box 220 K
W
D5200/D5360
PROG CONN
Incorrect wiring will
damage this equipment.
Suitable for dry indoor
use o nly.
Devices powered by the
AUX power output must
be supervised.
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000:
UL Listed and Classified control unit Model D9412GV2, D7412GV2, or D7212GV2;
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;
UL Listed Local Bell
PROGRAMMABLE
ALARM OUTPUTS
Term inals
SWITCHED AUX
and
67
Te r mi na l
8
Reset Pin
Disable All Except Battery
Charging And Programming
27
PROG
CONN
26
25
24
2
1
1 - Locked (Closed) 2 - Unlocked (Open)
Figure 5: Area 5 Silent Alarm Relay in RPS
4.5.4 D7212GV2 Ground Fault Specifications
Table 6 provides the impedance specifications for
detecting ground faults when any terminal or field
wiring is shorted to ground.
Table 6: Ground Fault Impedance
Specifications
Impedance Control Panel Detects Ground Fault
300 Ω
Yes
300 Ω to
200 kΩ
Detection depends upon the terminal
200 kΩ
No