D7212GV2 | Operation and Installation Guide | 12.0 SDI Devices
50 Bosch Security Systems, Inc. | 2/07 | F01U003805-02
The DX4010i can be installed up to 305 m (1000 ft)
from the control panel, using 0.8 mm (22 AWG) wire.
The DX4010i was not investigated by UL. Do not use
DX4010i in UL Listed installations.
The D9133 can be installed up to 305 m (1000 ft) from
the control panel using 1.2 mm (18 AWG) wire. The
D9133 was not investigated by UL. Do not use the
D9133 in UL Listed installations.
12.4.2 Address Settings
No jumper settings are required for the D9133 (SDI
Address 80) for home or building automation purposes
(Figure 24). Remove the jumper shunts for this purpose.
Figure 24: D9133 Jumper Setting for Address 80
1234
80
The DX4010i has specific DIP switch settings for SDI
Address 80 when home or building automation is
desired. Figure 25 shows the correct settings for
Address 80.
Figure 25: DX4010i DIP Switch Settings
SER
RxTx
BUS
Rx Tx
LED
ENABLE
DB9 GND
ENABLE
P1
P6
P2
P3
1 2 4 8 16 32 64 128
ON
123456
78
1 2 4 8 16 32 64 128
ON
123456
78
1
2
3
4
1 - Address DIP switches
2 - OFF position
3 - ON position
4 - SDI Address 80 switch settings
12.4.3 Supervision
Supervision of the serial interface module is available
through programming. Supervision is not required to
use a DX4010i or a D9133.
If supervised, and the serial interface module does not
respond to control panel supervision polls, the control
panel sends an SDI Failure Report to the receiver. If it
fails to communicate with the DX4010i or the D9133,
SERVC SDI 80 displays at the keypad. The SDI
Failure Report includes the address of the troubled
module indicating which module needs service.
12.5 SDI Address 88
SDI Address 88 is available with the D7212GV2
Control Panel and is used for several different
applications. When using SDI Address 88, connect
only one listed device at a time.
12.5.1 D9133DC Direct Connect Programming
Module
Use the D9133DC Direct Connect Programming
Module to handle local programming of the
D9412GV2 and D7412GV2 Control Panels. In
addition, the D9133DC allows diagnostic and history
retrieval.
D9133DC is not UL Listed, and cannot
remain connected to the system for UL
applications.
Connecting the D9133DC
3.
1. Configure D9133DC for SDI Address 88. To
program the control panel when the reset pin is in
the unlocked position, program Enable SDI RPS to
Yes in the GV2AUX handler.
4.
2. Connect D9133DC to Com Port 1 or Com
Port 2 on the PC. The D9133DC has a DB-9
female serial connector. A null-modem cable must
be purchased separately to connect the D9133DC
to a PC.
5.
3. Using 0.8 mm (22 AWG) or 1.2 mm (18
AWG) wire, connect the D9133DC SDI terminals
(SDI PWR, SDI A, SDI B, and SDI COM) to the
control panel’s SDI terminals (Terminals 29 to 32).
To send or receive the control panel’s program, place
the Reset Pin in the Locked or Unlocked position.
Locking the Reset Pin when programming
the control panel improves the uploading
and downloading times.
Used as an External Modem
The D9133DC can operate as an external modem
when using Remote Programming Software (RPS) with
the control panel. Refer to the D9412GV2/D7412GV2
Program Entry Guide (P/N: F01U003636) for
programming details.