DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 99
Bosch Security Systems | 8/04 | 4998153891C
Options 2, Zone Function ##
Address: See Table 17 on page 88
Default: See Table 17 on page 88
Selections: 0 to 15
Enter This Data Digit to Select Options
Options 2, Zone Function 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Enabled
Swinger Shunt
• • • • • • • •
Alarm Output
Can Be Bypassed or Force Armed
• • • • • • • •
Cross-Zone
• • • • • • • •
Swinger Shunt: If enabled, this option activates Swinger Shunt functions for Alarm Output (Functions 1|5,
1|8 to 1|12, and 8|8) and Zone Reporting. See Swinger Count for Zone Reports on page 105 for additional
Swinger information.
Alarm Output: If enabled, this option activates the alarm output functions (Output Function 1|8 to 1|12, and
8|8, see Output Parameters on page 107) for alarm events.
Can Be Bypassed or Force Armed: Only zones assigned to a Zone Function with this option enabled can be
bypassed or force armed. Bypassed zones remain bypassed for the arming cycle. Force armed zones return to
the system automatically if they restore during the arming cycle. 24-hour zones (fire and non-fire) can be
made bypassable with this option.
Cross-Zone: If enabled, this option creates a Cross-Zone Zone Function type using the following conditions:
When any zone assigned to the Cross-Zone Function detects a pulse, the control panel starts a 60-second
timer.
If a second zone assigned to the same Cross-Zone Function detects a pulse, the control panel creates a
Cross-Zone Alarm event for both zones.
A second pulse on the first zone does not create an alarm event.
If a single pulse on a Cross-Zone lasts 20 sec, the control panel creates an alarm event for that zone only;
it is not a Cross-Zone event.
If programmed for unverified event reporting (see Zone Response Options on page 103), the control panel
sends an Unverified Cross {17} or a Fire Unverified {77} report when a pulse is detected without another
cross zone pulse to verify it. The Unverified event is not sent until the 60-second timer that starts when
the first zone is violated has expired.
Do not configure 24-Hour Door and 24-Hour Fire with Alarm Verification zone function types as Cross-
Zones.