SC9000
ST150 SAFECOM Central Station Operations Manual
© 2002 Radionics Page 27 4998122249B
•
Panel Arm XLAT assigns the Panel Arm output to one of the 80 output translation lines.
•
Output1 XLAT assigns the specified control to one of the 80 output translation lines.
NOTE: See SYSTEM OUTPUT for more information.
•
Output XLAT - 00 to 4F: The Output Translation Table (XLAT) specifies the English plain text definition that you wish
to assign to an OUTPUT. The text will be displayed in place of the default messages “Enabled” or “Disabled”. The
Output Translation Table has 5 pages, with 16 line numbers per page, for a total of 80 line numbers. Each line
provides a maximum of 8 characters for English text translation for Enable and Disabled Output conditions. The
corresponding text assigned to the respective Output in the translation table is only for display at the SC9000
computer. It is not part of the message sent to the Automation software. Output translation gives the operator the
ability to allow an Output on SC8016 to report “PUMP ON” or “PUMP OFF” instead of “OUTPUT ENABLED” or
“OUTPUT DISABLED”. This ability can be very useful for remote control applications. Each translation table (XLAT)
line contains two available conditions that the operator must define, “ENABLED” & “DISABLED”.. These are the only
conditions an SC8016 output can be in and report.
NOTE: The SAFECOM ST150 v1.00 and higher software default values for all new Radio Communicator outputs are “ 00
“ and the default values for line #00 in the Output Translation Table are enabled and disabled.
4.2.3 Remote Status Display-the SC8016 Radio Communicator’s Response to a Manual “Poll” by the
Operator.
If the central station operator performs a manual poll of a Radio Communicator, the remote status display comes up on
the screen to show the operator the exact status of the Radio Communicator in the field. The Remote Status display
allows the operator to individually control and monitor the status of a SC8016. The following is a description of those items
available for viewing and control on the Remote Status display
(See the diagram below and the explanation following):