Bosch AMAX panel 2000 ICP-AMAX-P Manual de instalación Pagina 37

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 92
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 36
AMAX panel 2000 / AMAX panel 2000 EN Fault and Tamper Description | en 37
Bosch Sicherheitssysteme GmbH Installation Manual F.01U.241.127 | V4 | 2011.12
The Tamper condition is reset when the Keypad is closed and Tamper condition is reset.
Supervise:
1. Report the Tamper condition to configured destination on Location 140 when the
Tamper Condition is detected.
2. Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
3. When the Tamper Condition is reset, send the restored report to the configured
destinations. The FAULT indicator is turned off when there is no other system fault.
5.7.4 Keypad lock out
Condition:
Invalid code is entered more times than allowed by the code retry attempts (programmed in
location 179)
Restore:
Keypad lock out is reset when the Keypad lockout time (3min) is expired and the fault is reset.
Supervise:
1. Report the Keypad lock out to configured destination on Location 140 when the Keypad
lock out is detected.
2. Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
3. When the Keypad lock out Condition is reset, send the restored report to the configured
destinations.The FAULT indicator is turned off when there is no other system fault.
5.7.5 Sensor Tamper
Condition:
Tamper contact is triggered (Zone is programmed as Dual End of Line)
Restore:
Tamper contact is restored and Tamper condition is reset.
Supervise:
1. Report the Sensor Tamper to configured destination on Location 140 when the Sensor
Tamper is detected.
2. Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
3. When the Tamper condition is reset, send the restored report to the configured
destinations. The FAULT indicator is turned off when there is no other system fault.
Sensor Tamper Zone Indication
The zone indicator 5 lights to indicate Sensor Tamper conditions.
Enter [5] to step to Zone Indicator list to identify the Zone where the Sensor Tamper comes
from.
1=Zone 1 2=Zone 2 3=Zone 3 4=Zone 4 5=Zone 5 6=Zone 6 7=Zone 7 8=Zone 8
5.7.6 Zone Tamper
Condition:
Tamper contact (direct connected to the Zone) is triggered (Zone type = Tamper)
Restore:
Tamper contact is restored and Tamper condition is reset.
Supervise:
1. Report the Tamper condition to configured destination on Location 140 when the
Tamper condition is detected.
2. Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
3. When the Tamper condition is reset, send the restored report to the configured
destinations. The FAULT indicator is turned off when there is no other system fault.
Vista de pagina 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 91 92

Comentarios a estos manuales

Sin comentarios