90 en | Troubleshooting AMAX panel 2000 / AMAX panel 2000 EN
F.01U.241.127 | V4 | 2011.12 Installation Manual Bosch Sicherheitssysteme GmbH
Battery fault still
indicates after replaced
with new battery.
System test the battery each time arming or every time set
in location 191. Only after testing the battery fault can be
cleared away.
Voltage of the new battery reaches the normal value after it
is charged for some time.
Control Panel does not
dial.
Check if the dialing function is switched off in
communication programming (Telephone number and
transmission format need to be programmed).
No remote arming
function.
Check if the function is switched off (Do not set Location
152 and 153 as 0).
No RPS software
function.
Check if the function is switched off (Do not set Location
152 and 153 as 0).
Abnormal in PSTN/
Domestic dialling
communicaiton.
When extention system is used in telephone network,
dialing delay needs to be added in programming.
Network supports the ADSL at the same time, the control
panel needs to be connected through the ADSL filter .
Trouble Causes & Measures