Bosch ISW-BIT1-HAX WLSN INSTALLATION Especificaciones Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 60
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
wLSN | Reference Guide | 2.0 General Installation
12 Bosch Security Systems, Inc. | 3/07 | F01U009440-01
You must test the devices at the same EN50131 Security
Grade at which the control panel discovers the devices.
4. Find a suitable location for the hub base and apply power by
either connecting it to the control panel (refer to the control
panel’s installation instructions), or temporarily connecting a
9 VDC to 12 VDC battery.
5. Insert the wLSN Hub back into the base. Rotate the
enclosure locking mechanism to the locked position.
6. Proceed to the appropriate procedure:
- Section 2.4.2 RFSS Testing Between wLSN Hub and
Device
- Section 2.4.3 RFSS Testing Between wLSN Hub and
Installation Tool on page 14
You must use the Installation Tool with the wLSN Smoke
Detector. You cannot determine RFSS with the detector
itself.
2.4.2 RFSS Testing Between wLSN Hub and Device
1. Take the device being tested to its planned mounting
location.
2. Remove and re-insert the batteries of the device, then
quickly press and release the tamper switch button (refer to
Figure 1 on page 13) four times to enter RFSS mode.
You must enter RFSS mode within 10 sec of re-inserting
the batteries.
When RFSS mode is enabled, the LED lights steadily for 5 sec,
then flashes.