K2200 Series | User Guide | 6.0 Installer Commands EN | 46
Bosch Security Systems | 7/03 | 17376 v1.1 / 47491C
6.2 Alarm Event Manager and Relay
Outputs
6.2.1 Overview
The Alarm Event Manager is an optional alarm
module that can be attached to any reader channel. It
can be attached at any point in the cable between the
door controller and reader. The alarm module has 8
inputs and 8 relay outputs but relays 5 to 8 can only
administrated by Readykey for Windows.
8 Monitored Inputs
Each alarm module can monitor up to 8 inputs and
generate an alarm if any enabled input is activated.
Each input may be:
• Normally Open or Normally Closed (set on the
module itself)
• Enabled/Disabled Manually
• Enabled/Disabled using a time profile
• Programmed to activate a relay.
8 Relay Outputs
The 8 relay outputs on the module may be activated
by:
• An monitored input being activated.
• A system event.
• A time profile.
6.2.2 Identiying Modules, Inputs and Relays
Each reader channel on a door controller may have
an alarm module connected. This means a maximum
of 16 modules per system (four on each door
controller, although only two on a Readykey K1200).
Each alarm module has 8 possible inputs. These are
numbered 1 to 8 on each alarm module. When
reporting, however, the zone number, 1 to 128, is
used. The zone number is as shown in the following
table.
Table 21: Zone Number
Zone Numbers
Input Number:
Location
12345678
Door Controller 1
Alarm Module 1 1 2 3 4 5 6 7 8
Alarm Module 2 9 10 11 12 13 14 15 16
Alarm Module 3 * 17 18 19 20 21 22 23 24
Alarm Module 4 * 25 26 27 28 29 30 31 32
Door Controller 2
Alarm Module 5 3334353637383940
Alarm Module 6 4142434445464748
Alarm Module 7 * 4950515253545556
Alarm Module 8 * 5758596061626364
Door Controller 3
Alarm Module 9 65 66 67 68 69 70 71 72
Alarm Module 10 73 74 75 76 77 78 79 80
Alarm Module 11 * 81 82 83 84 85 86 87 88
Alarm Module 12 * 89 90 91 92 93 94 95 96
Door Controller 4
Alarm Module 13 97 98 99 100 101 102 103 104
Alarm Module 14 105 106 107 108 109 110 111 112
Alarm Module 15 * 113 114 115 116 117 118 119 120
Alarm Module 16 * 121 122 123 124 125 126 127 128
* Not available on Readykey K1200