
Security Escort | Installation and Setup Guide | 2.0
E
ui
ment Estimation
EN | 17
Bosch Security Systems | 1/09 | 33831E
Number of Outdoor Receivers
To estimate the number of receivers,
first read Section
2.3.3 Outdoor
Receiver Installation. Assume a
maximum receiver spacing of 90 m (300
ft.) between receivers, in both
directions, for receivers that are not
within 30 m (100 ft.) of a building
with inside coverage. Receivers within
30 m (100 ft.) of a building should be
spaced the same as receivers in the
building (spacing the outside
receivers at a somewhat larger spacing
is acceptable in most cases).
An outside area directly between two
buildings with inside protection needs
no additional receivers if the
buildings are 90 m (300 ft.) or less
apart. If the buildings are more than
90 m (300 ft.) apart the outside
receivers should evenly spaced between
the buildings. Make sure the standard
90 m (300 ft.) spacing is not
exceeded. For outside spacing adjacent
to a covered building, start the 90 m
(300 ft.) spacing at the building
wall.
Figure 3: Determining the Number of Outdoor Receivers Required
by
by by
by
by
by
byby
by
by
byby
by
by
by
by
by
by
by
by
byby
1
30 m
100 ft.
30 m
100 ft.
90 m
300 ft.
90 m
300 ft.
90 m
300 ft.
1 - Receivers
2 - Building 1
3 - Building 2
Allowance for Special Coverage
Requirements
For purposes of the bid, the number of
receivers estimated should be
increased by 5% to allow for special
coverage considerations and RF problem
areas.
Number of Transponders
Assume one transponder per building
for indoor installations. If wiring
can be run from other buildings or
from outdoor receivers, they can be
connected to one transponder. Never
exceed the total number of 64 devices
(receivers and alert units) per
transponder. All outside wiring must
be under ground or in metal conduit.
Number of Receiver and Alert Units per
Multiplex Bus
Although each bus can handle eight
receivers and alert units, it is a
good idea to leave some addresses
available on each bus to allow for
future expansion. For systems with a
high number of supervised
transmitters, see Section
3.2.4
Transponder Wiring Notes.
Multiplex Bus Wire
The multiplex bus should be wired with
four conductor 1.2 mm (18 AWG) wire.
The wire should not be paired or
shielded. In the United States this is
the same as fire system wire, except
it should not be red.
Comentarios a estos manuales