Standby Battery Requirements
For door controllers, the battery voltage
should match the lock output voltage.
Now that you know the total continuous current
requirement of the door controller plus readers, locks
and ancillaries, you should multiply this figure by the
number of hours standby needed.
In the enclosure supplied, there is room for two 12 V
7 Ah batteries. If this does not provide sufficient
backup, the batteries must be located outside the case
or the controller mounted in a larger case.
Note:
A door controller with a continuous current of 2 A will
require at least a 4 Ah battery to provide 2 hours cover
(2 A x 2 hours = 4 Ah).
The Ah rating of a battery is usually
determined when discharged over a 10
or 20 hour period. If a fully charged
battery is discharged over a shorter
period than this, as in the example above,
it will last for less time than its rating
suggests. You should consult the battery
manufacturer's correction factor charts to
determine a more accurate figure. than
expected.
Using an External Charger
In order that a fully discharged battery can recover to
a fully charged state within 24 hours, you should
consider using an external charger when using more
than a 7 Ah battery. Use the wiring shown below.
Note:
The auxiliary battery charger output must not exceed 2
VDC over K2200 battery output.
Figure 15: Using an External Battery Charger
7 Ah 7 Ah
K2200
Battery
5A Slow Blow 5A Slow Blow