K2200 Series | Installation Guide | 5.0 Installation Details EN | 32
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
Figure 18: Reader Wiring Diagram - In/Out Readers
Use the most appropriate reader for the location bearing in mind, internal or external, vandal resistance,
decor, panel mounting, etc.
Note:
The in/out reader option is only available if Readykey readers are used. If you are using Wiegand or Magstripe readers
and require in/out readers, you must use lock sharing where two reader channels operate the same lock.
Reader Fitting
See the documentation supplied with each Readykey
reader for specific details for fitting that type of
reader.
In general:
Readers should be mounted at a convenient
height, usually at about the height of a door
handle, on the unhinged side of the door.
Readers should be mounted at least 3.3 ft. (1 m)
apart to prevent any interaction between them.
Be particularly careful with this distance when
placing readers on each side of the same door.
Consider future service requirements such as
access to cables, etc.
Reader Cabling
Use unshielded, multi-stranded, tinned copper signal
cable, the type commonly used in alarm installations.
A minimum of 24 AWG (0.5 mm), cable is required
(reader, request to exit and door contact). For
example, some readers have a sounder which require
an additional core to make use of the feature.
The maximum reader cable length is dependent on
both the reader type and cable gauge as detailed
below. For example, the cable length for the Mullion
and standard plus readers is:
Full details are provided in the documentation
supplied with each reader.
Table 14: Appropriate Wire Gauge based on
Length
Length Wire Gauge
up to 750 ft. (250 m) 24 AWG (0.5 mm)
up to 1500 ft. (500 m) 20 AWG (1.0 mm)
up to 3000 ft. (1000 m) 18 AWG (1.2 mm)
Four conductors are used to connect the reader itself,
the other conductors can be used for the optional
request to exit and door monitoring signals (see
Section 5.4.3 Request to Exit (DR2) on page 34 and see
Section 5.4.4 Door Monitoring (DR1) on page 34).