Bosch K2200 Series Guía de instalación Pagina 54

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 60
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 53
K2200 Series | Installation Guide | 7.0 Troubleshooting EN | 54
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
7. Connect the reader to another channel, if the
reader now operates, the original channel is
faulty. Arrange for the door controller to be
repaired. Go to step 10.
8. Disconnect the suspect reader. Disconnect the
reader connector at the door controller. Check
the cable for short circuits between all
conductors, and all conductors and ground.
9. If the cable is to the correct gauge and free from
short circuits, connect the known working reader
in place of the suspect reader. If this reader
operates, the original is faulty. Arrange for a
replacement with your supplier.
10. Repeat for all four (two on a Readykey
K2200)
reader channels.
7.1.4 Checking the Lock Output
If all the reader channels are shown to operate
correctly, you should check the lock outputs. You
should know whether the lock is fail-safe (power is
removed to operate the device) or fail-secure (power
is applied to operate the device. You should also
know whether the door controller has been set to
provide 12 VDC or 24 VDC. If interlock has been
set on a pair of readers, channels 1 and 4 will operate
lock output 1, and channels 2 and 3 will operate lock
output 2.
1. For each lock output:
Make sure that the door secure, that is, the door
controller display should not indicate that the
door is open.
Make sure a lock release time has been set, it
should be at least 5 seconds to allow
measurements to be reliably made.
Establish whether lock sharing has been set.
2. Check the voltage at the lock output (L-, L+) on
the controller. This should be 12 VDC or 24
VDC if the lock is fail-safe, or less than 0.5
VDC if it is fail-secure. (The Readykey
K2200
series has solid state lock outputs, these will not
show exactly 0 volts when off).
3. Operate the lock, operate the RTE or short the
DR2 reader input to GND. The lock output
should operate. Check the voltage at the lock
output. This should now show the reverse of the
previous measurement, i.e. less than 0.5 VDC for
fail-safe, 12 VDC or 24 VDC for fail-secure. If
not, suspect the lock output to be faulty.
4. Repeat steps 2 and 3 above but this time
measure the voltage at the lock. The lock should
receive the minimum voltage required for it to
operate (see the lock manufacturer's
specifications). If the voltage is too low at the
lock, the lock supply cable gauge may be too
small for the distance from the controller.
5. Disconnect the cable from the lock. Check the
cable for short circuits between the conductors,
and between the conductors and ground.
6. Ensure there is a Metal-Oxide Varistor (MOV)
fitted across the lock terminals. If large currents
are used (i.e. >1 A) use the large MOV supplied
with the door controller. If small currents are
used (i.e. <1 A) use the small MOV supplied
with the reader. Reconnect the lock.
7. Check the current drawn by the lock. This
should not exceed 2.0 A (12 VDC) or 1.0 A (24
VDC). If it significantly exceeds the nominal
current specified by the manufacturer, the lock
may be faulty.
8. If the lock still fails to operate when the door
controller is switching the correct voltage,
suspect a faulty lock. Try fitting a known working
lock in place of the suspect device.
9. Repeat for all four (two on a Readykey K1200)
lock outputs.
D/C n ERROR-1 (where n is 2 - 8).
This means the master is trying to communicate
with a slave controller that has been entered in
the poll table, but is getting no reply.
10. Check:
The six-wire bus connection between the master
and slave.
Check the option switches (bottom left of door
controller circuit board) are set correctly. The top
three switches should be to the right on the
master, to the left on a slave.
Check the address of the slave, it should be set to
2, 3 or 4. Make sure no other slaves have the
same address.
Disconnect any other slaves on the six-wire bus.
If the fault goes away, check the connections and
addresses of the other slaves.
7.1.5 No error is displayed on the master but
the slave still fails to communicate
This probably means that the slave door controller is
not in the master's poll table.
Check:
The poll table should include the slave controller
number (2-8). Use the INST command (see
Section see Section 6.1.2 INIT Command) to check
the poll table.
Vista de pagina 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 60

Comentarios a estos manuales

Sin comentarios