Bosch AMAX panel 4000 EN Guía de instalación Pagina 52

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 176
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 51
Zone normal: Activate Disarm
Wiring Diagram for Key-switch Zone: short for arm. The momentary time is capable of lasting
Min. 300ms.
COM
Zone
Wiring Diagram for Key-switch Zone: short for arm. The momentary time is capable of lasting
Min. 300ms.
COM
Zone
When the key-switch operates the Arm/Disarm, the keypad sounds two beeps and report sent
to the system by User Code 254
Notice!
As the key-switch operates the arm/disarm successfully, the siren sounds short to indicate it.
16 - Delay Exit
The delay exit zone will perform as below:
1. DISARM: Same as Instant zone disarm status
2. AWAY Arm:
Zone normal - no Alarm / no report
Zone triggered - Entry time starts - no Alarm / no report
Disarming during entry time - no Alarm / no report
Zone triggered - during exit time - no Alarm / no report / abbreviates remaining time
for exit to 5 s
Zone triggered - during entry time - no Alarm / no report
Zone triggered - entry time is expired - Alarm / report (report is delayed for 30sec,
when system is disarmed before, no report)
3. STAY ARM: Same as AWAY ARM performance.
First delay zone will start the entry time; all other delay zones will follow.
When System is disarmed and zone is not restored before, a Zone restore report is
sent.
17 - Interior Delay Exit
The Interior delay exit zone will perform as below:
1. Disarm: same as the Instant Zone disarm status
2. AWAY Arm: same as the Delay Exit Zone AWAY Arm status
3. STAY Arm:
This Zone will be Ignored and performed as disarm.
52 en | Settings
AMAX panel 4000 / AMAX panel 4000
EN
2013.07 | 03 | F.01U.267.112 Installation Guide Bosch Sicherheitsysteme GmbH
Vista de pagina 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 175 176

Comentarios a estos manuales

Sin comentarios