3. When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
RF Receiver 1 Jammed
Condition:
Much disturb signal around the receiver if wireless module is enable.
Restore:
No much disturb signal around the receiver and wireless module is enable and fault is reset.
Supervise:
1. Report the receiver jam fault to configured destination when the fault is detected.
2. Slow flash FAULT indicator (refer to the detailed description in chapter keypad
indicators)
3. When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
RF Sensor Failure
RF Sensor Missing
Condition:
Any one wireless zone no status report to receiver in the RF supervision interval and wireless
module is enable.
Restore:
All wireless zones have status report to receiver in the RF supervision interval and wireless
module is enabled and fault is reset.
Supervise:
1. Report the wireless zone missing fault to configured destination when the fault is detected.
2. Slow flash FAULT indicator (refer to the detailed description in chapter keypad indicators)
3. When the fault is reset, send the restored report to the configured destinations. The FAULT
indicator is turned off when there is no other system fault.
RF Sensor Fault
Condition:
Any one wireless zone is abnormal (e.g. Remove the pyro from the smoke detector/...) and
wireless module is enable.
Restore:
All wireless zone are normal and wireless module is enabled and fault is reset.
Supervise:
1. Report the wireless zone fault to configured destination when the fault is detected.
2. Slow flash FAULT indicator (refer to the detailed description in chapter keypad indicators)
3. When the fault is reset, send the restored report to the configured destinations. The FAULT
indicator is turned off when there is no other system fault.
RF Repeater Failure
1-8 RF Repeater 1-8 Missing
Condition:
No status report to receiver in the RF supervision interval and wireless module is enable.
Restore:
Have status report to receiver in the RF supervision interval and wireless module is enable and
fault is reset.
Supervise:
1. Report the repeater missing fault to configured destination when the fault is detected.
2. Slow flash FAULT indicator (refer to the detailed description in chapter keypad indicators)