You can program the Exit Timer from 0 to 255 sec in increments of 1 sec. When arming the
system in AWAY Mode, the remote codepad beeps during Exit Time until the final 10 sec, when
the codepad sounds one continuous beep to indicate the end of Exit Time is near.
The remote codepad always sounds one short beep at the end of Exit Time when arming in
STAY Mode1 or STAY Mode 2.
Entry Guard Timer for STAY Mode
Location 472 to 473
Location Default
Increments of 1 sec (0 sec to 15 sec) 472 0
Increments of 16 sec (0 sec to 240 sec) 473 0
Entry Guard Timer for STAY Mode is the delay time used for all zones except 24-Hour Burglary
and 24- Hour Fire Zones when the system is armed in STAY Mode 1 or STAY Mode 2. All zones,
including Delay Zones, use this timer for the entry delay (for example, the Entry Guard Timer
overrides the delay time programmed for a Delay Zone). If the Entry Guard Timer is
programmed as 0, each zone acts according to its programmed zone type.
Delay Alarm Reporting Time
Location 474 to 475
Location Default
Increments of 1 sec (0 sec to 15 sec) 474 0
Increments of 16 sec (0 sec to 240 sec) 475 0
These locations program the time in sec that a delayed report waits dormant in the buffer
before it is sent to the receiving party. If a User Code holder resets the alarm within this time
frame, the control panel clears the communicator buffer and does not report the alarm to the
receiving party.
Sensor Watch Time
Location 476 to 477
Location Default
Increments of 1 sec (0 sec to 15 sec) 476 0
Increments of 16 sec (0 sec to 240 sec) 477 0
The time set in these two locations determines the number of days (0 to 99) a zone can
remain sealed before registering as a fault. This feature is active only when the system is
disarmed. If a zone programmed for Sensor Watch is not unsealed and reset during this time,
the FAULT indicator lights.