
Forced Arming
Arming the system when a zone is not sealed is known as forced arming. Refer to
Section14.3.7Zone Options2on page 63 to enable forced arming for each zone.
If the STAY indicator does not light and a long beep sounds when you attempt to arm the
system in STAY Mode 1, forced arming is not permitted. If this is the case, you must seal all
zones or manually isolate them before you can arm the system.
Disarming the system from STAY Mode 1
There are two methods to disarm the system from STAY Mode 1. You can always use the first
method. You can use method two only if Option 4 is enabled in Location 497 (refer to
Section18.6Consumer
Options2on page 83).
To disarm the system from STAY Mode 1 (method one):
1. Enter your code and press [STAY].
2. Two beeps sound and the STAY indicator is extinguished. The system is now disarmed.
To disarm the system from STAY Mode 1 (method two):
A flashing zone indicator represents a previous alarm in that zone. If this is the case, a valid
User Code is required to disarm the system using method one. To enable method two, Option
4 in Location 497 must
be enabled (refer to Section18.6ConsumerOptions2on
page 83).
1. Press and hold [STAY].
2. When two beeps sound, release the button.
The STAY indicator is extinguished and the system is disarmed.
Notice!
Single button disarming from STAY Mode 1 reports as User Code 00.
Arming the system from STAY Mode 2
STAY Mode 2 is used when you need to arm the perimeter and unused areas of the premises
to detect a would-be intruder from entering the premises, while at the same time being able to
move freely within an area that is automatically isolated.
You can program zones to be automatically isolated in STAY Mode 2 using an Installer Code
function (refer to Section5.1.5) or a Master Code function (Section5.2.6).
If the system reports to a base station, it sends a
Partial Close Report (Contact ID Event Code 456).
Entry Guard Timer for STAY Mode
When arming the system in STAY Mode 2, an optional entry timer called Entry Guard Timer for
STAY Mode can be used to delay the sirens, strobe, and bell outputs if a zone that is not
automatically isolated activates an alarm. Entry Guard Timer for STAY Mode is the delay time
used for all zones, except 24-Hour zones, when the system is armed in STAY Mode 1 or STAY
Mode 2.
If the Entry Guard Timer for STAY Mode is programmed and a zone that was not automatically
isolated is activated, the codepad beeps twice per sec until the Entry Guard Timer for STAY
Mode expires or the system is disarmed. If the alarm is not reset before Entry Guard Timer for
STAY Mode expires, the strobe, bell, and siren outputs are activated into alarm.
6.4
6.5
54 en | System Operations Control Panel
2014.07 | 00n | F01U298026 Installation Guide
Comentarios a estos manuales