ECODRIVE Drive Controller DKC02.1
2-2 Error Diagnostic Messages DOK-ECODRV-SSE-03VRS**-WAR1-EN-P 12.96
F207 Switching to uninitialized operation mode
Cause:
"0" has been programmed in at least one of the four mode parameters S-
0-0032..35. This mode has been selected by bits 8 and 9 in the master
control word while the drive controller was activated.
Remedial action:
Enter the required mode in the activated mode parameter.
Valid modes are:
Meaning: Bit list of mode parameters:
Torque control 0000 0000 0000 0001
Velocity control 0000 0000 0000 0010
Position control with position
feedback value 1
0000 0000 0000 x011
Position control with position
feedback value 2
0000 0000 0000 x100
Drive-internal interpolation with
position feedback value 1
0000 0000 0001 x011
Drive-internal interpolation with
position feedback value 2
0000 0000 0001 x100
Fig. 2-1: Modes
Parameter: Primary mode S-0-0032
Secondary mode 1 S-0-0033
Secondary mode 2 S-0-0034
Secondary mode 3 S-0-0035
Verify that a valid interpolation type has been entered.
F218 Heatsink Overtemperature Shutdown
Description:
The heat sink temperature of the DKCs is monitored. The unit is switched
off to prevent damage if the heat sink temperature is too high.
Cause:
1. The ambient temperature is too high. The specified performance
characteristics are valid up to an ambient temperature of 45°C.
2. The heat sink of the DKC is polluted.
3. Other modules or cabinet installation prevent convection.
4. Fan defective