DOK-ECODRV-SSE-03VRS**-WAR1-EN-P • 12.96 Error Diagnostic Messages 2-3
Remedial action:
Ref. 1. Reduce ambient temperature (provide cooling for the switchgear
cabinet, for example)
Ref. 2. Clean the heat sink
Ref. 3. Install the unit in a vertical position and provide sufficient
clearance for the ventilation of the heat sink.
Ref. 4. Replace the unit
F219 Motor Overtemperature Shutdown
The drive generates this error message when the motor temperature
exceeds 150°C.
Cause:
1. Motor overload. The effective torque requested from the motor
has exceeded the permissible continuous torque value for too
long a time.
2. Broken wire or short-circuit in the cable to the motor temperature
monitor.
3. Instability in the speed control loop.
Remedial action:
Ref. 1. Verify motor rating. Check whether the drive conditions of a
system that has been used for a long time have changed in the
meantime (pollution, friction, moved masses, etc.).
Ref. 2. Check the cable to the motor temperature monitor (X6/1 and
X6/2) for broken wires or short-circuit.
Ref. 3. Check the parameter values of the speed control loop (see
Functional Description).
F220 Bleeder Overtemperature Shutdown
Description:
Overload of the built-in brake resistance. The drive is shut down after
braking if the maximum braking energy is exceeded. This protects the
bleeder from thermal destruction.
Cause:
1. The energy returned from the mechanical system of the machine
via the motor is too high.
Remedial action:
Ref. 1. Too much power ---> reduce acceleration values
Too much energy ---> reduce velocity values
Verify drive rating
Install additional bleeder module if necessary