ECODRIVE Drive Controller DKC02.1
DOK-ECODRV-SSE-03VRS**-WAR1-EN-P 12.96 Error Diagnostic Messages 2-15
F879, Crossing Velocity Limit (S-0-0091) Value
In torque control mode, the actual velocity is monitored. This error is
generated if the velocity that has been programmed in the parameter S-
0-0091, Bipolar Velocity Limit Value is exceeded (1.125-fold value,
minimum 100 rpm).
Cause:
The command torque is higher than the load torque. This causes the
actual velocity to be increased up to the maximum possible motor speed.
Remedial action:
Assign the correct torque command value for the required task. Reduce
the parameter S-0-0092, Bipolar Torque/Force Limit Value.
F895 4 kHz Fault
Description:
The 4-kHz signal that is used for producing the resolver signals is
synchronized with software processing. This error message is generated
in the case of a synchronization error.
Cause:
1. Incorrect synchronization of resolver excitation voltage and
software
2. The error could be caused by an electrostatic discharge.
Remedial action:
Ref. 1. Replace the drive controller and return it to the factory for
inspection
Ref. 2 Cycle the power to all units off and back on. If this does not lead
to a positive result: Replace the drive controller and return it to
the factory for inspection