ECODRIVE Drive Controller DKC02.1
DOK-ECODRV-SSE-03VRS**-WAR1-EN-P 12.96 Command Diagnostic Messages 4-5
C114 T4 > TScyc (S-0-0002) - T4min (S-0-0005)
Cause:
The maximum value permitted for S-0-0007, Feedback Acquisition
Starting Time (T4) is:
S-0-0002, SERCOS Cycle Time - S-0-0005, Minimum
Feedback Acquisition Time (T4min)
The value of S-0-0007, Feedback Acquisition Starting Time (T4) is
incorrect.
Remedial action:
Correct S-0-0007, Feedback Acquisition Starting Time (T4). The
definition of this parameter is within the responsibility of the controller
manufacturer and is specified by the SERCOS interface.
C115 T2 too small
Cause:
The selected value of S-0-0089, MDT Transmit Starting Time (T2) is
incorrect. The drive cannot work with the value.
Remedial action:
Correct S-0-0089, MDT Transmit Starting Time (T2).
The definition of this parameter is within the responsibility of the
controller manufacturer and is specified by the SERCOS interface.
C200 Communication phase 4 transition check
Meaning:
The command S-0-0128, C2 Communication phase 4 transition
check has been activated.
C201 Invalid Parameter (-> S-0-0022)
Cause:
Communication parameters that are required for drive operation in
communication phase 4 are invalid. The invalid parameters are stored in
S-0-0022, IDN List of Invalid Op. Data for Comm. Ph. 3.
Remedial action:
Write to the invalid parameters of S-0-0022, IDN List of Invalid Op.
Data for Comm. Ph. 3 to make them valid.