4-62 Master Communication MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
See also descriptions of the respective parameters in the separate
documentation "Rexroth IndraDrive, Parameter Description"
Bit number in
signal status word
Configured
parameter Function/significance
0 P-0-0115 bit 1 status of device control "ready"
1 S-0-0330 bit 0 n_actual = n_command
2 S-0-0403 bit 0 status reference encoder
3 S-0-0331 bit 0 n_feedback = 0
4 S-0-0332 bit 0 nactual < nx
5 P-0-0115 bit 2 status of device control "warning"
6 S-0-0333 bit 0 T >= Tx
7 S-0-0334 bit 0 T >= Tlimit
8 S-0-0335 bit 0 n command > n limit
9 S-0-0336 bit 0 In position
10 S-0-0337 bit 0 P >= Px
11 … 15 --
Fig. 4-41: Example of configuration for main spindle messages via digital
outputs
See also section "Spindle Positioning" in chapter "Drive Functions"
Diagnostic and Status Messages
Monitoring the Digital Inputs/Outputs
For the parallel interface different kinds of errors are monitored at the
inputs and outputs or ports. The following error situations can be
detected:
• undervoltage of 24 V supply
• incorrect polarity of the supply of a port
• overload of an output
• short circuit of an output
Note: There is only the collective message F2044 External power
supply X15 error for the above-mentioned errors of the
parallel interface.