MPH-02, MPB-02, MPD-02 Drive Functions 8-37
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
• fatal errors (F8xxx)
→ immediate torque disable
• fatal system errors (F9xxx)
→ immediate torque disable
Possible Drive Reactions
One of the following reactions for "best possible deceleration" can be set:
Reaction Value of P-0-0119
velocity command value reset ("emergency halt")
0
torque disable
1
velocity command value reset with ramp and filter
("quick stop")
2
return motion
1)
3
1)
… Only possible with enabled expansion package "servo function"!
Fig. 8-24: Parameterization options for "best possible deceleration"
See also Parameter Description "P-0-0119, Best possible
deceleration"
Velocity Command Value Reset ("Emergency Halt")
In the case of error, the closed-loop-controlled servo drive in velocity
control is shut down with command value = 0. The drive then brakes with
its maximum allowed torque (see also "Limitations: Current and Torque
Limitation" in chapter "Drive Control").
Note: In the case of open-loop-controlled U/f operation, the
shutdown at the torque limit only takes place, when the stall
protection loop has been activated (cf. P-0-0045, Control
word of current controller)! The maximum deceleration is
set by the value entered in P-0-0569, Maximum stator
frequency change.
P-0-0119 = 0